Replacing drives
4–9
Hitachi Unified Storage Hardware Service Guide
NOTE 1: User data cannot be backed up when a drive to be replaced is
blocked or when the drive belongs to a RAID Group that contains a blocked
drive.
NOTE 2: The red ALM LED on the drive goes OFF within about five
minutes after the drive is inserted into the drive slot on the storage system.
If the red ALM LED does not go OFF, remove the inserted drive from the
storage system, wait at least 30 seconds, and then insert it again.
NOTE 3: If the orange WARNNG LED is blinking slowly, visit the HDS
Support Portal at
.
NOTE 4: If the green READY LED on the front of the Controller Box is
blinking quickly for 30-to-50 minutes, 40-to-60 minutes for the CBL
Controller Box, or 80-to-180 minutes when the DBW is connected to the
CBL, wait for the LED to stop blinking before replacing drives.
Summary of Contents for CBL
Page 20: ...xx Hitachi Unified Storage Hardware Service Guide Labels on the CBXSS ...
Page 30: ...xxx Hitachi Unified Storage Hardware Service Guide CBL CBLE CBLD DBS DBSD DBL DBLD DBF ...
Page 39: ...xxxix Hitachi Unified Storage Hardware Service Guide Out ...
Page 40: ...xl Hitachi Unified Storage Hardware Service Guide ...
Page 152: ...5 8 Replacing a cache backup battery Hitachi Unified Storage Hardware Service Guide ...
Page 156: ...6 4 Replacing a Fan Module Hitachi Unified Storage Hardware Service Guide ...
Page 180: ...8 16 Adding and replacing controllers Hitachi Unified Storage Hardware Service Guide ...
Page 188: ...9 8 Replacing cache memory Hitachi Unified Storage Hardware Service Guide ...
Page 200: ...11 6 Replacing the Host connector Hitachi Unified Storage Hardware Service Guide ...
Page 204: ...12 4 Replacing the Drive I O Module Hitachi Unified Storage Hardware Service Guide ...
Page 212: ...14 4 Replacing the SAS ENC cable Hitachi Unified Storage Hardware Service Guide ...
Page 274: ...17 14 Troubleshooting Hitachi Unified Storage Hardware Service Guide ...
Page 291: ...1 Hitachi Unified Storage Hardware Service Guide ...