Parameterization
53/95
Parameter
Description
Value
Descriptions of the values
Presence
Presence in
SmartWire-DT network
Device shall be
present
Device must be present in current SmartWire-DT bus
configuration (default)
Device may be not
present
Device may be absent in current SWD bus
configuration
Type of sensor
input 0
Sensor selector (signal
range) input 0
Voltage (0-10V)
Voltage sensor (0-10 V) (default)
Current (0-20mA)
Current sensor (0-20 mA)
Type of sensor
input 1
Sensor selector (signal
range) input 1
Voltage (0-10V)
Voltage sensor (0-10 V) (default)
Current (0-20mA)
Current sensor (0-20 mA)
Type of actuator
output 0
Actuator selector
(signal range) output 0
Voltage (0-10V)
Voltage (0-10 V) (default)
Current (0-20mA)
Current (0-20 mA)
Type of actuator
output 1
Actuator selector
(signal range) output 1
Voltage (0-10V)
Voltage (0-10 V) (default)
Current (0-20mA)
Current (0-20 mA)
Measurement
update time
Refresh rate of
measured value
20 ms
100 ms (default)
200 ms
500 ms
Refresh rate of measured values to SmartWire-DT
network in milliseconds
Averaging
Mean value function
On
Averaging function to smooth out input signal
fluctuations (default)
Off
No averaging
Table 19: Configurable device options and parameters of SWD slave (EU5C-SWD-2A2A
example)
SmartWire-DT Gateway | EU5C-SWD-SERCOS
DOC160805UM01EN | Revision 1 | English | 2017-02 | Released | Public
© Hilscher 2017