Acyclical communication
61/95
10.3.2
Write request example
The following step-by-step instructions show how to reset the error counter
of SWD slave #1 to value
0
by using the IndraWorks
®
ML 14V10 P2
engineering tool.
·
SWD Index of error counter:
127
(hex:
0x7F
)
·
Request type for writing task:
1
(hex:
0x01
)
·
Length of data to be written in bytes:
1
(hex:
0x01
)
·
Data (value) to be written:
0
(hex:
0x00
)
Prerequisites
·
You are connected and logged-in at the Sercos PLC/Master via
IndraWorks.
·
The gateway is connected to the Sercos PLC/Master and is in
communication phase 4 (CP4).
Step-by-step instructions
1. Open parameter editor.