Technical data
90/95
Category
Parameter
Value
Supply voltage
U
AUX
Rated operational voltage
24 V DC
-15 % +20 %
Input voltage residual ripple
≤ 5 %
Protection against polarity reversal
Yes
max. current I
max
3 A
Note
: If contactors with a total power consumption >
3 A are connected, a power feeder module EU5C-
SWD-PF1/2 has to be used.
Short-circuit strength
No, external fuse FAZ Z3
Heat dissipation
Typ. 1 W
Potential isolation
No
Rated operating voltage of 24-V-DC
slaves
Typ. U
AUX
-0,2 V
Supply voltage
U
POW
Supply voltage
24 V DC
-15 % +20 %
Protection against polarity reversal
≤ 5 %
Protection against polarity reversal
Yes
Rated operational current I
111 mA (with two participants)
Heat dissipation at 24 V DC
2.66 W (with two participants)
Potential isolation between U
POW
and
15-V-SmartWire-DT supply voltage
No
Bridging voltage dips
10 ms
Repeat rate
1 s
Status display
POW
LED
SmartWire-DT supply
voltage
Rated operational voltage U
e
15 V ± 3 %
max. current I
max
0.7 A
Note
: If contactors with a total power consumption >
0.7 A are connected, a power feeder module EU5C-
SWD-PF2 has to be used.
Short-circuit strength
Yes
Connection supply
voltages
Connection type
Push-in terminals
solid
0,2 – 1,5 mm
2
(AWG 24 – 16)
Flexible with ferrule
0,25 – 1,5 mm
2
SmartWire-DT network
Participant type
SmartWire-DT master
SmartWire-DT Master ASIC
SWD-80P-RS485
Number of SmartWire-DT slaves
99
Baud rate
125 / 250 kBd
Address setting
Automatic
Status display
SmartWire-DT master:
SWD
LED, duo color red/
green
Configuration:
Config
LED, duo color red/green
Connections
Plug, 8-pole
Plug connectors
Blade terminal SWD4-8MF2
SmartWire-DT Gateway | EU5C-SWD-SERCOS
DOC160805UM01EN | Revision 1 | English | 2017-02 | Released | Public
© Hilscher 2017