Acyclical communication
57/95
10.2.2
Read request example
The following step-by-step instructions show how to read the error counter
of SmartWire-DT slave #1 by using the IndraWorks
®
ML 14V10 P2
engineering tool.
·
SWD Index of error counter:
127
(hex:
0x7F
)
·
Request type for reading task:
0
(hex:
0x00
)
·
Maximum length of expected response in bytes:
120
(hex:
0x78
)
Prerequisites
·
You are connected and logged-in at the Sercos PLC/Master via
IndraWorks.
·
The gateway is connected to the Sercos PLC/Master and is in
communication phase 4 (CP4).
Step-by-step instructions
1. Open parameter editor.
Ø
In the
Project Explorer
, select the gateway then click the
parameter
editor symbol in the tool bar.
Figure 22: Open parameter editor
Ê
The parameter editor opens.
SmartWire-DT Gateway | EU5C-SWD-SERCOS
DOC160805UM01EN | Revision 1 | English | 2017-02 | Released | Public
© Hilscher 2017