36
F.
If procedures call for a wet pump, open tank fill valve (removes trapped air).
Close valve after several minutes.
1.
Check apparatus for signs of leaks.
2.
4.4.3
Quarterly Maintenance
Perform the following procedure every three months.
4.4.3.1
Check Gearbox Oil Level
The gearbox is drained of oil at the factory prior to shipment. Check the gearbox oil level upon
receipt of the pump and then at least every three months. The gearbox needs to be filled with 1
to 1–1/2 qt (1.1 liter) of the gear oil listed in 5.7.2, Recommended Lubricants. (The amount de-
pends on gearbox position.) Figure 11 shows the typical gearbox oil fill, and level component lo-
cations as the gearbox is rotated through the available positions. Check the gearbox oil level via
the plug style sight glass.
Figure 12. Typical Gearbox Oil Fill/Level Component Locations
Typical Gearbox Oil Fill/Level Component Locations – CONTINUED
Perform the following procedure to check the oil level in the gearbox.
A.
Visually check gearbox oil level sight glass (Figure 11).
NOTE
The oil level should be the center of the sight glass.
Summary of Contents for AP
Page 2: ......
Page 28: ......
Page 71: ...59 Figure 19 One Piece Volute AP CBP MBP Figure 20 Three Piece Volute RSD...
Page 73: ...61 Figure 21 AP Pump Exploded View...
Page 74: ...62 Figure 22 CBP Pump Exploded View...
Page 75: ...63 Figure 23 MBP Pump Exploded View...
Page 76: ...64 Figure 24 RSD Pump Exploded View...
Page 77: ...65 Figure 25 Gearbox Exploded View All Except 3 74 1 GR...
Page 78: ...66 Figure 26 Gearbox Exploded View 3 74 1 GR...
Page 158: ...146 THIS PAGE INTENTIONALLY BLANK...
Page 174: ...C 12 THIS PAGE INTENTIONALLY BLANK...
Page 176: ...D 2 DATE HOURS RUN MAINTENANCE PROBLEM PART S USED REASON REPLACED INITIALS...