126
Model
Power supply
mode
Power components
Configured quantity
PEM
One is required for each power frame
Power monitoring module One is required for each power frame
AC power supply
•
6 at most for the S12504 or S12508
•
12 at most for the S12518
PSE9000-D DC
DC power frame
•
1 for the S12504 or S12508
•
2 for the S12518
Power monitoring module One is required for each power frame
DC power supply
•
6 at most for the S12504 or S12508
•
12 at most for the S12518
NOTE:
•
The AC power frame and power monitoring module are integrated to the chassis of S12500 AC models,
so you do not need to order them. You must order the PEM and AC power supplies yourself.
•
The DC power frame and power monitoring module are integrated to the chassis of S12500 DC models,
so you do not need to order them. You must order the DC power supplies yourself (PEM is not needed for
the DC power system).
Table 42
Electrical parameters of power supplies
Power supply Rated input voltage
range
Max input voltage
range
Max input
current
Max output power
AC power
supply
100 VAC to 120 VAC;
50 Hz or 60 Hz
200 VAC to 240 VAC;
50 Hz or 60 Hz
90 VAC to 264
VAC; 47 Hz to 63
Hz
13.3 A
1200 W (100 VAC to
120 VAC)
2000 W (200 VAC to
240 VAC)
DC power
supply
–48 VDC to –60 VDC
–42 VDC to –72
VDC
60 A
1800 W
Table 43
16A AC power cords used in different countries or regions
1
Connector
type
Code (Length)
Countries or regions
where the type of
power cords conforms
to local safety
regulations and can be
used legally
Other countries or
regions using this type of
power cords
Countries or
regions seldom
using this type of
power cords
I type
04043396 (3
m/9.84 ft)
Mainland China
Connector outline
Power cable outline
Connector outline
Summary of Contents for S12500 Series
Page 40: ...30 Figure 28 Installing an upper expansion cable management bracket 1 2 3 4 5 6 7...
Page 109: ...99 Figure 74 Replacing a card for the S12504 A Card to be removed B Card to be installed...
Page 149: ...139 Figure 85 Loopback operation on an optical transceiver...