APPENDIX
229
Specifications
Below are the basic conditions required to operate the GPM-8310
within specification:
Calibration: Yearly
Operating Environment:
18~28 ˚C (64.4~82.4˚F)
Humidity: <80%RH,
Accuracy: ± (% of r % of range)
The specifications apply when it warmed up for at least 30
minutes and operates in the slow rate.
The power supply cable must be grounded to ensure accuracy.
Input voltage and current must be standard sine wave.
The power factor must be 1.
The crest factor must be 3.
The common-mode voltage must be zero.
General Specifications
Specification Conditions:
Temperature: 23
˚
C±5
˚
C
Humidity: <80%RH(non-condensing)
Operating Environment: (0~40
˚
C)
Temperature Range: 30~40
˚
C, Relative Humidity: <70%RH(non-condensing);
>40
˚
C, Relative Humidity: <50%RH(non-condensing)
Indoor use only
Altitude: <2000 meters
Pollution degree 2
Storage Conditions (-40~70
˚
C)
Humidity: <90%RH(non-condensing)
General:
Power Source: 100-240 VAC 50/60Hz
Power Consumption: Max 30VA
Bench Dimensions: 268 mm (W) X 107 mm (H) X 379 mm (D) (w/t bumpers)
Weight: Approximately 2.9 kg
Summary of Contents for GPM-8310