GPM-8310 User Manual
38
Setting up method of calculating harmonics
Steps
1.
Press
Setup
button.
2.
Press
Enter
button.
3.
Press down arrow key to move
cursor to the
Harmonics
field.
4.
Use soft keys to select and confirm
the desired option.
Option
IEC Calculate the ratio of harmonic quantity of
the 2nd through the upper limit 50th
harmonic to the 1st harmonic. The HRM.I
status icon, for example, on the display
lights up in green when IEC is selected for
harmonics.
CSA Calculate the ratio of harmonic quantity of the
2nd through the upper limit 50th harmonic to
the 1st through the 50th harmonic.
Off
Turn off the harmonic calculation function.
Default value
IEC
Steps
5.
Press right arrow key to move
cursor to
Order
field.