Conventional Optical
Smoke Detector
C-9102
F
eatures and Benefits
1.
Sensing chamber for exceptional dust
proof ability
2.
Built-in Remote Indicator Output
3.
Twin LED for 360
º
vision
4.
Low profile design
Description
With the technique of scattering, the
detector's reliability, stability and consistency
are improved. The special chamber design
ensures the insert-defend, dirt-defend and
anti-light disturbance.
The conventional type can be used directly
with our conventional fire alarm panels.
Using an interface (I-9319), it can be
connected to our intelligent panels.
Technical Specifications
•
Standard: EN54-part7
•
Approval: LPCB,UL,CE
•
Protection rating: IP 32
•
Detecting Range:80m² at 6-12meter
ceiling height; and 60m² below
6meter
•
•
Operating voltage: 24Vdc (9Vdc to
24Vdc) polarized
•
Operating Current:
Stanby: 0.1mA; Alarm:8mA
•
Operating temperature: -10°C to
+50°C
•
Relative humidity: 95%
•
Application: Indoor use
•
Material and colour: ABS, off-white
•
Wiring: 1 pair polarized
•
Dimensions: diameter 10cm; height
5cm
Selection of compatible Control Panels
Compatible with all GST Conventional panel
and GST Intelligent Fire Alarm Panels using
Zone monitor module:
Detector Installation
It is installed onto a standard one gang
electrical box with a mounting hole that
have 6.5cm spacing. Point the detector in
the base by the mark-line and secure the
detector in that position by rotates it
clockwise until it reaches the next mark line.
EMBEDDED BOX
CONCRETE PAD OR
HOLDING PAD
LED INDICATOR
MARK−LINE
ROTATE CLOCKWISE
2ND MARK−LINE
Wiring and Connection
Connect the wires to the required terminal
according to the wiring diagram. Using
active end of line can connect up to 15
detectors and base with diode. Using 4.7K
Ω
end of line resistor can connect up to 25
detectors.The cable must be fire rated type
and the size depends on the distance and
application. Minimum size gauge
1.0mm²(18 AWG).
1
2
3
4
FROM CONTROL PANEL
TO NEXT DEVICE
1 PAIR FIRE CABLE
1 PAIR FIRE CABLE
HOLE
HOLE
C−9314P Remote Indicator
−
+
Ordering Information:
Part
No
Description Weight
/Kg
Pack Qty
per Box
C-9102 Conventional
Optical
Smoke Detector
0.12 120
DZ-03 Detector
Base
-EOLR 0.05
360
DZ-03D Base with Diode AOL
0.05
360
MANUFACTURED IN ACCORDANCE WITH
Note: Specifications are subject to change without notice.
1
2
3
4
1
2
3
4
C−9101 SMOKE/HEAT DETECTOR
1
2
3
4
P−9907 ACTIVE
C−9102 SMOKE DETECTOR
END OF LINE
+
−
CONVENTIONAL
PANEL
OR
ZONE
MONITOR
MODULE