Conventional
Ultraviolet Flame
C-9104
Features:
1.
Not sensitive by sunlight
2.
Dust /corrosion/humidity resistance
3.
Secure and speedy communication
4.
Standard calibration set to detect a
3cm flame at 6metres
5.
Effective range 12 metres
6.
110
º
effective detection dispersion
angle
7.
Twin LED for 360
º
vision
Description:
The C-9104 Conventional Ultraviolet Flames
Detector is fast and capable to detecting the
ultraviolet (UV) rays emitted by a burning
substance and is used in high hazard
applications such as petrochemical plants,
munitions factories and other areas where
flammable or explosive liquids or solids are
handled or stored. The C-9104 sensor adopts
an ultraviolet photosensitive tube, with
qualities of highly sensitive, reliable, dust-
resistant, corrosion-proof and moisture-
resistant, therefore is not sensitive in sunlight,
dust, oil, tolerance of fume, and humidity.
Tec
hnical Specifications
•
Protection rating: IP 32
•
Operating voltage: 24Vdc
•
Operating Current:
Standby current 1.5mA
Alarm Current 10mA
•
Operating temp:-10°C to +50°C
•
Relative humidity: 95%
•
Application: Indoor use
•
Detection angle: 80 degree
•
Visual Indicator: LED, Red ( lit steady
when alarm
•
Material and colour: ABS, off-white
•
Wiring: 1 pair polarized
•
Dimensions: diameter 10cm; height
5cm
Selection of compatible Control Panels
Compatible with all GST Conventional panel
and GST Intelligent Fire Alarm Panels using
Zone monitor module:
Detector Installation
The combination of fire detection should be
installed complied with all local codes and /
or NFPA 72 National Fire Alarm Code, NFPA
70 National Electrical Code. Verify the
proper wiring and base is firmly mounted to
prevent detector damage before the
installation. Point the detector in the base
by the mark-line and secure the detector in
that position by rotates it clockwise until it
reaches the next mark line.
EMBEDDED BOX
CONCRETE PAD OR
HOLDING PAD
LED INDICATOR
MARK−LINE
ROTATE CLOCKWISE
2ND MARK−LINE
Wiring and Connection
Connect the wires to the required terminal
according to the wire diagram with
matching active end of line (P-9907).and
(DZ-03D) required base is The cable must
be fire rated type and the size depends on
the distance and application. Minimum size
gauge 1.0mm²(18 AWG)
Ordering Information:
Part No
Description Weight
/Kg
Pack
Qty per
Box
C-9104 Conventional
Ultraviolet Flame
Detector
0.123 120
DZ-03 Detector
Base
-EOLR 0.05 360
DZ-03D
Base with Diode AOL
0.05
360
MANUFACTURED IN ACCORDANCE WITH
Note: Specifications are subject to change without notice.
1
2
3
4
1
2
3
4
C−9101 SMOKE/HEAT DETECTOR
1
2
3
4
P−9907 ACTIVE
C−9102 SMOKE DETECTOR
END OF LINE
+
−
CONVENTIONAL
PANEL
OR
ZONE
MONITOR
MODULE