background image

 

30312264 

     

                                                                                       

                         

  Issue 1.06

 

                                       

 

Features

 

 

Strong environmental adaptability due to drift compensation. . 

 

Reed switch testing.   

 

Removable 

innovative 

sensing 

chamber, 

easy 

for                   

maintenance. 

 

Fire LED allows 360

°

viewing. 

    Remote indicator output available.   

 

2 levels sensitivities programmable; fix temperature or rate of rise 
programmable.

 

 

2  levels  smoke  sensitivities  programmable,  level  1  complies  with 
EN 54-7. Heat part complies with EN 54-5. 

Description

 

DC-9101E  Conventional  Combination    Heat

 

Photoelectric

 

Smoke

 

Detector, non-addressable, is a kind of combination detector consisting of 
smoke  sensing  parts  and  semi-conductor  heat  sensing  parts  in 
technological structure and circuit structure. 
Together with DP-9907, it can connect to conventional fire alarm control 
panel  or  connect  with  intelligent  fire  alarm  control  panel through  I-9319 
Addressable  Zone  Monitor  Unit  conduct  the  processing  of  detector 
signals.  The  detector  has  the  advantages  of  both  conventional 
photoelectric detector and rate of rise and fixed temperature heat detector. 
Just because of the combination of smoke detector and heat detector, it 
overcomes  the  non-sensitivity  to  dark  smoke  particles  of  ordinary 
scattering photoelectric detectors. It can also pick up fire with obvious rise 
of  temperature  such  as  alcohol  flame,  thus  extending  the  application 
range. 

Connection and cabling

 

The base is shown in Fig. 2.

 

C

B

A

 

Fig. 1                                Fig. 2

 

There are four terminals with numbers on the base. 

1: Detection zone positive IN 
2: Detection zone positive OUT 
3: Detection zone negative IN and OUT 
2: Positive terminal of remote indicator 
4: Negative terminal of remote indicator 

Recommended Wiring 

1.0mm

or  above  fire  cable  for  all  terminals  laid  through  metal  conduit  or 

flame proof conduit, subject to local codes. 

Note: Different color cables are used to avoid wiring mistake. 

Installation

 

Fix the flame retardant base with two taping screws. Then align A on the 
bottom of the detector to B of the base, and rotate the detector clockwise 
to mark C (Refer to Fig.1 and Fig. 2 for mark A, B, C).

 

Mounting of the detector is shown in Fig.3.

 

Electrical Box

Conduit

Detector

51.5mm

Orientation Base

 

Fig. 3 

 

 

Application

 

Warning:  The  alarm  current  depends  on  the  current  limit  of  the 
control panel. 24VDC cannot power the detector directly. Otherwise 
the detector will be blown up for lack of current limit resistor.

 

Rate of Rise , sensitivity level 1 and polling LED status is

 

“ON” are default. 

which can be modified by P-9910B programmer. Refer to P-9910B Hand 
Held Programmer Installation and Operation Manual for details.   
In power-on state, input unlocking password and press 

Clear

 to unlock. 

Press 

Function

, then number “3”, the screen shows “-” at the last digit.   

Input  corresponding  sensitivity  or  parameter  and  press 

Program

,  the 

screen  will  show  a  “P”,  the  corresponding  sensitivity  or  parameter  is 
programmed.  Press 

Clear

  to  clear  the  "P".  Input  locking  password  and 

press 

Clear

 to return. 

 

Table 1 Parameters Setup 

Parameter    Smoke 

Sensitivity 

Heat Part 

Polling LED 

Status 

Rate of Rise 

ON 

Rate of Rise 

ON 

129 

Rate of Rise 

OFF 

130 

Rate of Rise   

OFF 

Read  Sensitivity  Level:  in  power-on  state,  pressing 

Test

the  screen 

displays address of the detector. Pressing “

Up”,

 display sensitivity level, 

device type and initial sensitivity in turns.

 

 

When  the  detector  connects  with  conventional  fire  alarm  control 

panel or addressable zone monitor unit from GST, and if DP-9907 Active 
End  of  Line  Unit  is  connected  to  the  end  of  output  loop,  DB-01D  base 
should be used.

 

 

Used  as  the  detector  base,  DP-9907  Active  End  of  Line  is 

used  to  be  installed  a  conventional  detector  on  it.  The  system 
connection is shown in Fig. 4.

 

 

Fig. 4 

  When  DP-9907  Active  End  of  Line  Unit  is  not  used  as  the 

detector  base,  a  cover  should  be  added  to  it.  The  system 
connection is shown in Fig.5. 

Fig. 5 

DC-9101E Conventional Combination 

  Heat

 

Photoelectric

 

Smoke

 

Detector

 

2831-CPR-F0338 

GST-0507-01 

              14 

548q/03 

Summary of Contents for C-9101

Page 1: ...Alarm Panels using Zone monitor module Detector Installation It is installed onto a standard one gang electrical box with a mounting hole that have 6 5cm spacing Point the detector in the base by the...

Page 2: ...l and GST Intelligent Fire Alarm Panels using Zone monitor module Detector Installation It is installed onto a standard one gang electrical box with a mounting hole that have 6 5cm spacing Point the d...

Page 3: ...design Technical Specifications Protection Rating IP55 Operating Voltage 24VDC Operating current Standby Current 0 Alarm Current 30mA Operating Environment Temperature 10 50 C Relative Humidity 95 Con...

Page 4: ...al Specifications Operating voltage 24Vdc non polarized Operating Current 24Vdc Standby current 10mA Action current 160mA Operating temp 10 C to 50 C Flashing Frequency 20x180 per min Alarm Volume SPL...

Page 5: ...the power supply as well as the cathode of next detector 4 connects with the cathode of remote indicator Recommended Wiring 1 0mm2 or above fire cable for all terminals laid through metal conduit or...

Page 6: ...in Fig 10 b Clean the sensing chamber by alcohol cotton swab clipped by tweezers and also by clear water and brush Please note not to leave any cotton in the chamber c Install the sensing chamber and...

Page 7: ...l and GST Intelligent Fire Alarm Panels using Zone monitor module Technical Specifications Standard EN54 part 11 Approval LPCB CE Protection rating IP 40 Operating voltage 24Vdc Loop Operating current...

Page 8: ......

Page 9: ...Panels using Zone monitor module Detector Installation It is installed onto a standard one gang electrical box with a mounting hole that have 6 5cm spacing Point the detector in the base by the mark...

Page 10: ...imensions diameter 10cm height 3 5cm w o cover 4 5cm w cover Sounder Installation The sounder base should be installed in compliance with all local codes or NFPA 72 National Fire Alarm Code NFPA 70 Na...

Page 11: ...zone monitor unit is powered up and in normal operation the unit is acting as a load to produce periodic plus minus alternating differential pulse signals Due to the voltage dividing of current limiti...

Page 12: ...stem is back in operation 7 If a unit fails in testing check its connection and test again If it still fails return for repair VII Troubleshooting 1 The system alarms fault after power up Check power...

Page 13: ...eration and suitable for 92 MCP series The C 92FC constructed of high plastic quality with a modern pleasing appearance Technical Specifications Material and colour transparent flexi glass Dimensions...

Page 14: ...eration and suitable for 92 MCP series The C 92FC constructed of high plastic quality with a modern pleasing appearance Technical Specifications Material and colour transparent flexi glass Dimensions...

Page 15: ...the detector directly Otherwise the detector may be damaged for lack of current limit resistor The default class of the detector is A1R and polling LED status is ON which can be modified using a handh...

Page 16: ...e metal component on the PCB against damp and improper distortion Do fire simulation test at least once every 6 months Specification Operating Voltage 24VDC 16VDC 28VDC Standby Current 60 A Alarm Curr...

Page 17: ...her alarms in a common alarm network up to 30 alarms or can be interfaced to other systems Technical Specifications Power Supply PP3 H6F22 DC9V battery Indicator Red flashes in every 50 seconds in nor...

Page 18: ......

Page 19: ...CONTENTS I Description 1 II Specification 1 III Structure 2 IV Mounting and Wiring 3 V Application 6 VI Troubleshooting 7 VII Maintenance 8 VIII Cautions 8 IX Warranty Limited 9...

Page 20: ...Alarm State 5 0 W 3 Output capacity and control mode Voltage contact For 12VDC one way pulse solenoid whose driving capability is 1000 F capacitance discharge Volt free contact Volt free normally open...

Page 21: ...st the LEDs will flash in turn and the buzzer will sound three times 8 Life of Sensor 5 years 9 Operating Environment Temperature 10 50 Relative Humidity 95 non condensing 10 Dimension 121mm 87mm 47mm...

Page 22: ...depends on where the gas stove is There are still some principles to follow The detector and the gas stove should be placed in the same room The detector detecting natural gas or coal gas should be mo...

Page 23: ...use the detector and avoid any possible fault please do not mount the detector at following locations a Where affected by exhaust steam or oil smoke from the stove b Where near strong airflow such as...

Page 24: ...d g Where the detector is partitioned with the gas devices 2 Terminals are shown in Fig 3 Fig 3 K1 K2 Volt free normally open contact it is closed when alarming V V Connects with pipe solenoid or mech...

Page 25: ...Applying power supply to the detector after wiring and checking the green LED flashes 3 6 minutes for warm up and then it will light constantly for normal monitoring 2 Alarming When the monitored gas...

Page 26: ...ull it open manually 3 Fire Alarm Treatment When the detector alarms please immediately open the windows for ventilation Put out any fire do not make new fires Avoid switching on or off any electric a...

Page 27: ...ominated on its label 2 Don t install the detector at locations with high temperature near stoves or too much oil smoke near kitchen ventilator Keep environment around the detector clean 3 The detecto...

Page 28: ...e normal work after more than 5 hours with power on IX Warranty Limited GST warrants that the product will be free from defects in design materials and workmanship during the warranty period This warr...

Page 29: ...com cn GST UK Global System Technology PLC Lion Court Staunton Harold Hall Melbourne Road Ashby de la Zouch Leicestershire England LE65 1RT Tel 44 1283 225 478 Fax 44 1283 220 690 Email info gst uk co...

Page 30: ...solenoid valve driving ability 1000 F capacitance discharge Passive Contact Passive normally open contact capacitance 220V 1A for controlling connected devices Alarm Density Natural Gas 5500ppm 11 LEL...

Page 31: ...cording to the wire diagram K1 K2 Normally open passive contact which will be closed when the detector alarms V V Connects with pipe solenoid If the detector had alarmed for 3 to 7 seconds there would...

Page 32: ...ator Red not lit in normal operation and constantly lit when alarming Monitoring Area When space height is 6m 12m the monitoring area of a detector is 80m2 for normal protection area When space height...

Page 33: ...DZ 03 DZ 03D...

Page 34: ...i wire fire alarm developed from SCM Those with signal output interface board has a passive normally open alarm output contacts and fault output contact on each zone They have two external control out...

Page 35: ...d Of Line resistor 4 7K or AEOL Active End Of Line No of Sounder Output 2 Sounder Output Current 1 Ampere 500mA per output Sounder Output Voltage 20Vdc to 28 Vdc Aux Power Output 20Vdc to 28 Vdc Appli...

Page 36: ...d has a passive normally open alarm output contacts and fault output contact on each zone The two kind panels have six control output points through which it can control some devices such as sounder s...

Page 37: ...A Fire Alarm Output Output voltage 20Vdc 28Vdc Output current 0 5 A Fault Output Capacity Passive contact output 24vdc 1 A Aux Power Output 20Vdc to 28 Vdc 0 5A Repeater Panel Outpt 10mA Zone Capacity...

Page 38: ...ons diameter 10cm height 5cm Selection of compatible Control Panels Compatible with all GST Conventional panel and GST Intelligent Fire Alarm Panels using Zone monitor module Detector Installation The...

Page 39: ...ce from the detector With built in intelligent microprocessor the detector has strong ability of analysis and judgment The detector is ideally suited to historical buildings warehouses large storages...

Page 40: ...e cable must be fire rated and the size depends on the distance and application The minimum size gauge 1 0mm Selection of compatible Control Panels Compatible with all GST Intelligent Fire Alarm Panel...

Page 41: ...GST Conventional panels Wiring and Connection Connect as per the marking on the base Technical Specifications Standard EN54 part 11 Approval CE Protection rating IP 40 Operating voltage 24Vdc Loop Ope...

Page 42: ...retardant base with two taping screws Then align A on the bottom of the detector to B of the base and rotate the detector clockwise to mark C Refer to Fig 1 and Fig 2 for mark A B C Mounting of the d...

Page 43: ...also by clear water and brush Please note not to leave any cotton in the chamber c Install the sensing chamber and top cover back 5 Before cleaning notify the proper authorities that the system is und...

Page 44: ...e checking for short circuit or broken circuit It can also identify the location of detecting zone Installation and operation of the panel are very simple All control functions are realized through a...

Page 45: ...rol Mode Passive normally open closes and self locks after alarming and contact rated capacitance 1A 30VDC Indicator Red not lit in normal operation and constantly lit when alarming Operating Environm...