SMOKE ALARM DESCRIPTION
Model KF10, KF10LL
Ionisation 230V AC smoke alarm with 9V
battery back-up and Hush Button
Model KF10R
Ionisation 230V AC smoke alarm with recharge-
able battery backup and Hush Button
Model KF20,KF20LL
Optical 230V AC smoke alarm with 9V
battery back-up with Hush Buttonl
Model KF20R
Optical 230V AC smoke alarm with rechargeable
battery back-up and Hush Button
SMOKE ALARM FEATURES
• Interconnects with up to 23 other models, KF1, KF1R, KF2, KF2R, KF3, KF3R,
KF10, KF10LL, KF10R, KF20, KF20LL, KF20R, KF30, KF30LL, KF30R, 4870,
4881, 4973, 4985, 4892, 4899, 1SFW, 1SFWR, 2SFW, 2SFWR, 3SFW, 3SFWR,
and 4MCO and 4MDCO Mains CO alarms. Unique power connector prevents
interconnection with incompatible smoke alarms or security systems.
• Tamper-resist bracket quickly snaps into place and serves as a safeguard
against tampering.
• Multi-purpose green and red LEDs indicate that the smoke alarm is receiving
AC power, working under normal operation, in alarm, or under Hush Button.
• Loud alarm horn—85 decibels at 3 metres (10 feet)—sounds to alert you of
an emergency.
• Test button checks smoke alarm operation.
• All models feature Hush Button, which, when activated, quiets unwanted alarms
for up to 9 minutes.
• Models KF10, KF10LL, KF20 and KF20LL will not attach to the mounting
bracket if a battery is not in the battery pocket. These models will also sound
a short beep about once a minute if the battery is weak or improperly con-
nected.
• Models KF10R , KF20R , KF10LL and KF20LL have lithium batteries that will
last the life of the alarm and a tamper-proof locking screw option.
• Models KF10R and KF20R include permanent rechargeable lithium
batteries.
• Operating temperature: 0°C to 40°C
• Operates up to 93% humidity (non-condensing)
IMPORTANT SAFETY INFORMATION
PLEASE READ AND SAVE THESE
INSTRUCTIONS
W
A
R
N
I
N
G
•
DO NOT paint or cover the smoke alarm with tape.
•
This smoke alarm should be out of the reach of children.
•
AC smoke alarms require constant 230V AC, 50Hz power to operate
properly.
Mains-powered smoke alarms WILL NOT work if AC power is not
connected or has failed or been interrupted for any reason. Models KF10,
KF10LL and KF20, KF20LL require a working 9-volt battery to operate prop-
erly in the event of a power failure. Models KF10R and KF20R require a
minimum of 2 full days under mains power to reach full backup capacity. DO
NOT use any other kind of battery except as specified in this user guide. DO
NOT connect this smoke alarm to any other type of smoke alarm or auxiliary
device, except those listed in this user guide.
•
DO NOT remove or disconnect battery or turn off AC power to quiet
unwanted alarms.
This will remove your protection. Open windows or fan the air
around smoke alarm to silence it. KF10, KF10LL, KF10R, KF20, KF20LL and
KF20R smoke alarms feature a Hush Button which, when activated, will quiet
unwanted alarms for up to 9 minutes.
1
User Guide
PLEASE READ AND SAVE
INSTALLER: Please leave this user guide with the product.
KF10
KF10LL
KF10R
Ionisation
KF20
KF20LL
KF20R
Optical
EN14604:2005
LICENSE NO. KM 524754
0086-CPD-535595
14
EN 14604:2005
!
1374-7205-00(KF10_KF20_KF10R_KF20R)_EN_V4:_ 2014.11.20 10:16 AM Page 1