Conventional
Reflective Beam
Detector
C-9105R
Mounting the Detector
The detector can be mounted in 2 ways: the
installed onto standard two gang electrical
box, or directly by drilling the holes and
fixing with plugs.
Wiring and Connection
Connect the wires to the required terminal
according to the wire diagram. The D1,D2
is for 24VDC power supply. The K11,k12 for
fire alarm output contact (passive). The
cable must be fire rated and the size
depends on the distance and application.
The minimum size gauge 1.0mm
²
Selection of compatible Control Panels
Compatible with all GST Intelligent Fire
Alarm Panels GST 200, GST 5000, GST
9000 with interface module. Compatible
with all GST Conventional Fire Alarm
Control panel
Ordering Information:
Part No
Description
Weight
/Kg
Pack
Qty
per
Box
C-9105R Conventional
Reflector Beam
Detector
1.3 10
MANUFACTURED IN ACCORDANCE WITH
Note: Specifications are subject to change without notice.
D1 D2
TO POWER SUPPLY
24VDC
K22 K21K12 K11
FIRE ALARM
OUTPUT
CONTACT
(TO FACP)