background image

 

30312280   

         

                                                                                             

                     

Issue 1.07

 

30°

Testing 
Area

Fig. 8

  When  the  detector  is  connected  with  conventional  FACP  or 

addressable zone monitor unit, if a 4.7k

Ω

end of line resistor is 

connected to the end of output loop, DB-01 base is used. The 
system composition is shown in Fig. 6.   

 

Fig. 6

 

  When  multiple  detectors  are  connected  with  a  remote 

indicator, a diode 1N5819 should be connected to Terminal 4 
of the orientation base in series before going to the positive of 
the remote indicator. System composition is shown in Fig. 7.   

   

Fig. 7 

Maximum  15 detectors can  be connected to  the output of  zone 
monitor unit. In case of broken circuit or removal of any detector, 
the unit will transmit a fault message to the FACP. If and AEOL is 
connected, normal operation of other device in the system will not 
be affected. 

Testing 

Note:  Before  testing,  make  sure  the  detector  is  properly 
installed and powered up.    Testing can only begin after the 
detector is powered up for 10 seconds.   

The  detector  must  be  tested 
after  installation  and  regular 
maintenance.  The  methods  are 
as follows: 
(1) Reed switch testing 
The testing area of the detector 
is shown in Fig. 8.   
Approach the commission tool to 
the  testing  area  of  the  detector 
and  hold  for  several  seconds 
until the detector alarms. 
(2) Temperature test 
Approach a heater (such as a hair drier) to the thermistor of the 
detector until it alarms. 
After  testing,  disconnect  power  to  the  detector  for  over  10 
seconds to reset it. Notify the proper authorities that the system is 
back to normal operation. 
If a detector fails in testing, clean it by the steps in “Maintenance”, 
and retest it. If it still fails, return it for repair. 

Maintenance 

  The detector should be installed just before commission and 

kept well  before  installation,  taken corresponding  measures 
for dust-proof, damp-proof and corrosion-proof. 

  The dust cover cannot be removed until the project has been 

plunged into usage.   

  Clean  the  detector  at  least  once  a  year  to  ensure  normal 

operation of the system. 

  Before cleaning, notify the proper authorities that the system 

is  undergoing  maintenance  and  will  temporarily  be  out  of 
service. Disable the zone or system undergoing maintenance 
to avoid unwanted alarms. 

  The  detector  should  be  tested  again  after  cleaning  and 

re-installing. 

 

  Protect the metal component on the PCB against damp and 

improper distortion. 

 

  Do fire simulation test at least once every 6 months.

 

Specification 

Operating Voltage 

24VDC(16VDC~28VDC) 

Standby Current 

60μA 

Alarm Current 

55mA 

Fire LED 

Red, periodically flash once in 
polling when the status is set to 
“ON”; don’t illuminate when the 
status is set to “OFF”. Periodically 
flash twice in fault; illuminate in 
alarming.   

Remote Indication 
Output

 

Polarity-sensitive, directly 
connecting with remote indicator 
(built in 10k resistor in series, 
maximum output current is 2.0mA);   
The remote indicator does not 
illuminate in normal and flashes in 
alarm.   

Class and Setup   

Classes 

A1R, 

A2S, 

BS 

programmable. 

Maximum Ripple 
Voltage 

2V ( peak-to-peak) 

Alarm Reset 

Instantaneous cut-out (10s Min, 
1.0VDCMax.) 

Wiring 

Polarized two wire   

Ingress Protection 
Rating 

IP2X 

Ambient Temperature 

Class A1: -10

~+50

 

Class A2: -10

~+50

 

Class B: -10

~+65

 

Typical Fixed 
Temperature 

Class A1:    58

 

Class A2:    62

 

Class B:      77

 

Relative Humidity 

≤95%, non-condensing 

Material   

ABS 

Dimensions 

Diameter: 100mm 
Height: 53.3mm (with base) 

Mounting Hole Spacing 

45mm~75mm 

Weight 

About 110g (with base) 

Accessories and Tools 

Module 

Name 

Remarks 

P-9910B 

Handheld Programmer 

Order separately 

DB-01 

Base 

Order separately 

DB-01D 

Base 

Order separately 

DP-9907   

Active End of Line Unit   

Order separately 

T-MT 

Commission Tool 

Order separately 

WEEE Information 

2012/19/EU  (WEEE  directive):  Products  marked  with  this 
symbol cannot be disposed of as unsorted municipal waste 
in  the  European  Union.  For  proper  recycling,  return  this 
product  to  your  local  supplier  upon  the  purchase  of 
equivalent  new  equipment,  or  dispose  of  it  at  designated 
collection points. 

Limited Warranty

 

GST

 warrants that the product will be free from defects in design, 

materials  and  workmanship  during  the  warranty  period.  This 
warranty shall not apply to any product that is found to have been 
improperly  installed  or  used  in  any  way  not  in  accordance  with 
the instructions supplied with the product. Anybody, including the 
agents, distributors or employees, is not in the position to amend 
the contents of this warranty. Please contact your local distributor 
for products not covered by this warranty. 

 

This Data Sheet is subject to change without notice. Please contact GST for more information or questions. 

Gulf Security Technology Co., Ltd. 

No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004 

Tel: +86 (0) 335 8502434   Fax: +86 (0) 335 8502532        [email protected]   www.gst.com.cn 

 

Summary of Contents for C-9101

Page 1: ...Alarm Panels using Zone monitor module Detector Installation It is installed onto a standard one gang electrical box with a mounting hole that have 6 5cm spacing Point the detector in the base by the...

Page 2: ...l and GST Intelligent Fire Alarm Panels using Zone monitor module Detector Installation It is installed onto a standard one gang electrical box with a mounting hole that have 6 5cm spacing Point the d...

Page 3: ...design Technical Specifications Protection Rating IP55 Operating Voltage 24VDC Operating current Standby Current 0 Alarm Current 30mA Operating Environment Temperature 10 50 C Relative Humidity 95 Con...

Page 4: ...al Specifications Operating voltage 24Vdc non polarized Operating Current 24Vdc Standby current 10mA Action current 160mA Operating temp 10 C to 50 C Flashing Frequency 20x180 per min Alarm Volume SPL...

Page 5: ...the power supply as well as the cathode of next detector 4 connects with the cathode of remote indicator Recommended Wiring 1 0mm2 or above fire cable for all terminals laid through metal conduit or...

Page 6: ...in Fig 10 b Clean the sensing chamber by alcohol cotton swab clipped by tweezers and also by clear water and brush Please note not to leave any cotton in the chamber c Install the sensing chamber and...

Page 7: ...l and GST Intelligent Fire Alarm Panels using Zone monitor module Technical Specifications Standard EN54 part 11 Approval LPCB CE Protection rating IP 40 Operating voltage 24Vdc Loop Operating current...

Page 8: ......

Page 9: ...Panels using Zone monitor module Detector Installation It is installed onto a standard one gang electrical box with a mounting hole that have 6 5cm spacing Point the detector in the base by the mark...

Page 10: ...imensions diameter 10cm height 3 5cm w o cover 4 5cm w cover Sounder Installation The sounder base should be installed in compliance with all local codes or NFPA 72 National Fire Alarm Code NFPA 70 Na...

Page 11: ...zone monitor unit is powered up and in normal operation the unit is acting as a load to produce periodic plus minus alternating differential pulse signals Due to the voltage dividing of current limiti...

Page 12: ...stem is back in operation 7 If a unit fails in testing check its connection and test again If it still fails return for repair VII Troubleshooting 1 The system alarms fault after power up Check power...

Page 13: ...eration and suitable for 92 MCP series The C 92FC constructed of high plastic quality with a modern pleasing appearance Technical Specifications Material and colour transparent flexi glass Dimensions...

Page 14: ...eration and suitable for 92 MCP series The C 92FC constructed of high plastic quality with a modern pleasing appearance Technical Specifications Material and colour transparent flexi glass Dimensions...

Page 15: ...the detector directly Otherwise the detector may be damaged for lack of current limit resistor The default class of the detector is A1R and polling LED status is ON which can be modified using a handh...

Page 16: ...e metal component on the PCB against damp and improper distortion Do fire simulation test at least once every 6 months Specification Operating Voltage 24VDC 16VDC 28VDC Standby Current 60 A Alarm Curr...

Page 17: ...her alarms in a common alarm network up to 30 alarms or can be interfaced to other systems Technical Specifications Power Supply PP3 H6F22 DC9V battery Indicator Red flashes in every 50 seconds in nor...

Page 18: ......

Page 19: ...CONTENTS I Description 1 II Specification 1 III Structure 2 IV Mounting and Wiring 3 V Application 6 VI Troubleshooting 7 VII Maintenance 8 VIII Cautions 8 IX Warranty Limited 9...

Page 20: ...Alarm State 5 0 W 3 Output capacity and control mode Voltage contact For 12VDC one way pulse solenoid whose driving capability is 1000 F capacitance discharge Volt free contact Volt free normally open...

Page 21: ...st the LEDs will flash in turn and the buzzer will sound three times 8 Life of Sensor 5 years 9 Operating Environment Temperature 10 50 Relative Humidity 95 non condensing 10 Dimension 121mm 87mm 47mm...

Page 22: ...depends on where the gas stove is There are still some principles to follow The detector and the gas stove should be placed in the same room The detector detecting natural gas or coal gas should be mo...

Page 23: ...use the detector and avoid any possible fault please do not mount the detector at following locations a Where affected by exhaust steam or oil smoke from the stove b Where near strong airflow such as...

Page 24: ...d g Where the detector is partitioned with the gas devices 2 Terminals are shown in Fig 3 Fig 3 K1 K2 Volt free normally open contact it is closed when alarming V V Connects with pipe solenoid or mech...

Page 25: ...Applying power supply to the detector after wiring and checking the green LED flashes 3 6 minutes for warm up and then it will light constantly for normal monitoring 2 Alarming When the monitored gas...

Page 26: ...ull it open manually 3 Fire Alarm Treatment When the detector alarms please immediately open the windows for ventilation Put out any fire do not make new fires Avoid switching on or off any electric a...

Page 27: ...ominated on its label 2 Don t install the detector at locations with high temperature near stoves or too much oil smoke near kitchen ventilator Keep environment around the detector clean 3 The detecto...

Page 28: ...e normal work after more than 5 hours with power on IX Warranty Limited GST warrants that the product will be free from defects in design materials and workmanship during the warranty period This warr...

Page 29: ...com cn GST UK Global System Technology PLC Lion Court Staunton Harold Hall Melbourne Road Ashby de la Zouch Leicestershire England LE65 1RT Tel 44 1283 225 478 Fax 44 1283 220 690 Email info gst uk co...

Page 30: ...solenoid valve driving ability 1000 F capacitance discharge Passive Contact Passive normally open contact capacitance 220V 1A for controlling connected devices Alarm Density Natural Gas 5500ppm 11 LEL...

Page 31: ...cording to the wire diagram K1 K2 Normally open passive contact which will be closed when the detector alarms V V Connects with pipe solenoid If the detector had alarmed for 3 to 7 seconds there would...

Page 32: ...ator Red not lit in normal operation and constantly lit when alarming Monitoring Area When space height is 6m 12m the monitoring area of a detector is 80m2 for normal protection area When space height...

Page 33: ...DZ 03 DZ 03D...

Page 34: ...i wire fire alarm developed from SCM Those with signal output interface board has a passive normally open alarm output contacts and fault output contact on each zone They have two external control out...

Page 35: ...d Of Line resistor 4 7K or AEOL Active End Of Line No of Sounder Output 2 Sounder Output Current 1 Ampere 500mA per output Sounder Output Voltage 20Vdc to 28 Vdc Aux Power Output 20Vdc to 28 Vdc Appli...

Page 36: ...d has a passive normally open alarm output contacts and fault output contact on each zone The two kind panels have six control output points through which it can control some devices such as sounder s...

Page 37: ...A Fire Alarm Output Output voltage 20Vdc 28Vdc Output current 0 5 A Fault Output Capacity Passive contact output 24vdc 1 A Aux Power Output 20Vdc to 28 Vdc 0 5A Repeater Panel Outpt 10mA Zone Capacity...

Page 38: ...ons diameter 10cm height 5cm Selection of compatible Control Panels Compatible with all GST Conventional panel and GST Intelligent Fire Alarm Panels using Zone monitor module Detector Installation The...

Page 39: ...ce from the detector With built in intelligent microprocessor the detector has strong ability of analysis and judgment The detector is ideally suited to historical buildings warehouses large storages...

Page 40: ...e cable must be fire rated and the size depends on the distance and application The minimum size gauge 1 0mm Selection of compatible Control Panels Compatible with all GST Intelligent Fire Alarm Panel...

Page 41: ...GST Conventional panels Wiring and Connection Connect as per the marking on the base Technical Specifications Standard EN54 part 11 Approval CE Protection rating IP 40 Operating voltage 24Vdc Loop Ope...

Page 42: ...retardant base with two taping screws Then align A on the bottom of the detector to B of the base and rotate the detector clockwise to mark C Refer to Fig 1 and Fig 2 for mark A B C Mounting of the d...

Page 43: ...also by clear water and brush Please note not to leave any cotton in the chamber c Install the sensing chamber and top cover back 5 Before cleaning notify the proper authorities that the system is und...

Page 44: ...e checking for short circuit or broken circuit It can also identify the location of detecting zone Installation and operation of the panel are very simple All control functions are realized through a...

Page 45: ...rol Mode Passive normally open closes and self locks after alarming and contact rated capacitance 1A 30VDC Indicator Red not lit in normal operation and constantly lit when alarming Operating Environm...

Reviews: