Conventional Fire
Alarm Panels
GST108/116
Technical Specification
Conventional Fire Alarm System
Part Number
GST 108
GST116
Operating voltage
220Vac
±
15% , 50hz
Standard
BS5839, Part 4, 1988 and EN 54 parts 2 and 4
Approval
CE, LPCB
Operating Temperature
-10°C to 40°C @ 95% relative humidity
Standby Baterries
7AH , 24hours monitoring state
Output Voltage
20Vdc to 28 Vdc
Static Loading Current
2.4mA ( when connected with 15 conventional detectors
Fire Alarming Resistance
150
Ω
-1.5K
Ω
( nominal 470
Ω
)
End Of Line
4.7K
Ω
or AEOL ( Active End Of Line)
Sounder Output
4:Output voltage: 20Vdc
~
28Vdc ; Output current: 1 A
Fire Alarm Output
Output voltage: 20Vdc
~
28Vdc ; Output current: 0.5 A
Fault Output Capacity
Passive contact output :24vdc / 1 A
Aux.Power Output
20Vdc to 28 Vdc, 0.5A
Repeater Panel Outpt
10mA
Zone Capacity
8 zone
16 Zone
Application Indoor
use
Materials and colour
Coated metal/Grey
Dimension
380mm x 320mm x 95mm
Typical Wiring Connection
Fig.1
Fig.3
Fig.2
Fig.1 Using End of Line resistor, in compliance with
EN/BS standard, when using EOL resistor, call points
should be wired before detectors, so that the removal of
any detector will not inhibit call point from operating.
Fig.2 Using Active End of Line, enables call points to be
installed in any location on zone as will not affected by
removal of detector (required base DZ-03D)
Fig.3 The same as fig.2 principle, using AEOL without
detector.