Conventional Dual
Heat Detector
C-9103
F
eatures and Benefits
1.
Fixed Temperature and Rate of Rise
Detection
2.
Built-in Remote Indicator Output
3.
Twin LED for 360
º
vision
4.
Low profile design
Description
C-9103 Conventional Rate of Rise and Fixed
Temperature Heat Detector (hereinafter
called the detector) checks ambient
temperature with the sensitive feature of
thermo-sensitive elements. With a built-in
SCM, it’s fixed with highly reliable fire judging
program. Special processing technology
ensures its stable and reliable operation.
Matching with P-9907 Active End of Line Unit,
it can connect with compatible fire alarm
controller to conduct the processing of
detector signals.
Technical Specifications
•
Standard: EN54-part5,part6
•
Approval: LPCB,CE
•
Protection rating: IP 32
•
Detecting Range: 30 sqm for normal
area; and 20 sqm for high risk
•
Operating voltage: 24Vdc (9Vdc to
24Vdc) polarized
•
Operating Current:
•
Stanby: 0.8mA; Alarm: 1.4mA
•
Operating temperature: -10°C to
+50°C
•
Relative humidity: 95%
•
Application: Indoor use
•
Material and colour: ABS, off-white
•
Wiring: 1 pair polarized
•
Dimensions:
diameter 10cm;
height 5cm
Selection of compatible Control Panels
Compatible with all GST Conventional panel
and GST Intelligent Fire Alarm Panels using
Zone monitor module:
Detector Installation
It is installed onto a standard one gang
electrical box with a mounting hole that
have 6.5cm spacing. Point the detector in
the base by the mark-line and secure the
detector in that position by rotates it
clockwise until it reaches the next mark line.
Wiring and Connection
Connect the wires to the required terminal
according to the wire diagram with
matching active end of line (P-9907).and
(DZ-03D) required base. Using active end
of line can connect up to 15 detectors and
base with diode. Using 4.7K
Ω
end of line
resistor can connect up to 25 detectors.
The cable must be fire rated type and the
size depends on the distance and
application. Minimum size gauge
1.0mm²(18 AWG)
1
2
3
4
FROM CONTROL PANEL
TO NEXT DEVICE
1 PAIR FIRE CABLE
1 PAIR FIRE CABLE
HOLE
HOLE
C−9314P Remote Indicator
−
+
Ordering Information:
Part No
Description
Weigh
t/Kg
Pack Qty
per Box
C-9103
Conventional Dual
Heat Detector
0.123 120
DZ-03 Detector
Base
-EOLR 0.05
360
DZ-03D
Base with Diode AOL
0.05
360
MANUFACTURED IN ACCORDANCE WITH
Note: Specifications are subject to change without notice.
EMBEDDED BOX
CONCRETE PAD OR
HOLDING PAD
LED INDICATOR
MARK−LINE
ROTATE CLOCKWISE
2ND MARK−LINE
1
2
3
4
1
2
3
4
C−9103 HEAT DETECTOR
1
2
3
4
P−9907 ACTIVE
C−9103 HEAT DETECTOR
END OF LINE
+
−
CONVENTIONAL
PANEL
OR
ZONE
MONITOR
MODULE