Conventional Manual
Call Point
C-9201
Features and Benefits
1.
Re-settable (non-breaking glass)
2.
Additional volt free contact
3.
Friendly installation and test
Description
Designed for the purpose of raising an alarm
manually once verification of a fire or
emergency condition exists, by pressing the
non breakable glass. Meets the standard
requirement of EN 54 part 11, European
Standard and approved by Loss Prevention
Certificate Board (LCPB).
The C-9201 constructed of high impact red
ABS with a modern pleasing appearance. The
terminating back box enables first fix
installation and termination leaving the fascia
with integral electronics to be simply plugged
into base at the time of commissioning. Non
breakable glass that can be reset with the
GST standard reset sucker.
The C-9201 operated via a micro-switch that
when pressed a signal will be transmitted
and the volt free contact will be latched.
Contain integral LED indicator to denote
operational mode.
Selection of compatible Control Panels
Compatible with all GST Conventional panels
Wiring and Connection:
Connect as per the marking on the base.
Technical Specifications
•
Standard: EN54-part 11
•
Approval: CE
•
Protection rating: IP 40
•
Operating voltage: 24Vdc Loop
•
Operating current:
Standby current 0.8mA
Alarm Current 2mA
•
Operating temperature: -10°C to
+50°C
•
N/O Output contact: 60Vdc, 0.1A
•
Contact resistance: 100m
Ω
•
Relative humidity: 95%
•
Application: Indoor use
•
Visual Indicator: LED, Red ( lit
steady when alarm, 3 sec interval
blinking at normal state)
•
Material and colour: ABS, red
•
Wiring: 1 pair polarized
•
Dimensions: 90x122x48.5mm
Mounting Base
The location of manual call point should be
installed in compliance with all local codes
and / or NFPA 72 National Fire Alarm Code,
NFPA 70 National Electrical Code. Surface
mount and it is installed onto a standard
one gang electrical box with a mounting
hole that have 52mm
~
68mm spacing.
Ordering Information:
Part No
Description
Weigh
t/Kg
Pack
Qty
per
Box
C-9201 Conventional
Manual Call Point
0.156 120
Note: Specifications are subject to change without notice.
1
2
3
4
C−9202 MANUAL CALL POINT
TO NEXT DETECTOR
OR
AEOL
+
−
CONVENTIONAL
PANEL
OR
ZONE
MONITOR
MODULE
K1 K2
O− 0+
I+ I−
DETECTOR
FIRE
ELECTRICAL
I−9201
MOUNTING
WALL
BACK BOX
SURFACE MOUNT
BASE