Conventional Fire
Alarm Panels
GST102/104
Technical Specification
Conventional Fire Alarm System
Part Number
GST 102
GST104
Operating voltage
220Vac
±
15% , 50hz
Standard
BS5839, Part 4, 1988 and EN 54 parts 2 and 4
Approval
CE, LPCB
Operating Temperature
-10°C to 40°C @ 95% relative humidity
Number of Zone
Two zone
Four Zone
Zone Capacity
15 detectors (AOL);25 detectors (EOLR)
Standby Batteries
5AH , 24hours monitoring state
Output Voltage
20Vdc to 28 Vdc
Static Loading Current
2.5mA ( when connected with 15 conventional detector
Fire Alarming Resistance
150
Ω
-1.5K
Ω
( normal 470
Ω
)
End Of Line resistor
4.7K
Ω
or AEOL ( Active End Of Line)
No. of Sounder Output
2
Sounder Output Current
1 Ampere (500mA per output)
Sounder Output Voltage
20Vdc to 28 Vdc
Aux.Power Output
20Vdc to 28 Vdc
Application Indoor
use
Materials and colour
Coated Metal / Grey
Dimension
380mm x 320mm x 95mm
Typical Wiring Connection
Fig.1
Fig.3
Fig.2
Fig.1 Using End of Line resistor, in compliance with
EN/BS standard, when using EOL resistor, call points
should be wired before detectors, so that the removal of
any detector will not inhibit call point from operating.
Fig.2 Using Active End of Line, enables call points to be
installed in any location on zone as will not affected by
removal of detector (required base DZ-03D)
Fig.3 The same as fig.2 principle, using AEOL without
detector.