5.7 Electrical connection
A direct connection of the system to the power supply is made
using the terminals 1 (L1), 2 (N) and 3 (PE). Depending on the
version, the power supply can be 230 V (AC) or 115 V (AC).
5.7.1 Terminal connection diagram
Fig. 12
Terminal connection diagram
5.7.2 Power supply
5.7.3 Potential-free outputs
5.7.4 8 V
Warning
The electrical connection must only be carried out by
qualified personnel.
Observe the local safety regulations!
Switch off the power supply before connecting the
mains cable.
Caution
Connection to an incorrect power supply may destroy
the system.
Note
Make the electrical connection according to the
enclosed connection diagram.
T
M
04
82
04
45
10
L
N
PE
Description
L
N
PE
Description
1
2
3
Power input
16
17
18
-------------------------------------------
4
5
6
Power output
19
20
21
7
8
9
-------------------
22
23
24
Solenoid valve/pump/bypass water
10
11
12
HCl dosing pump
25
26
27
Solenoid valve: enclosure exhaust
device
13
14
15
NaClO
2
dosing pump
28
29
30
Solenoid valve: exhaust device for
batch tank
Root
NO
Description
Function
31
33
Fault
31/33 open in case of fault
32
34
Pre-empty signal HCl/NaClO
2
32/34 open in case of pre-empty signal
37
39
Automatic
37/39 closed in case of "system active"
38
40
Tank run dry
38/40 open in case of dry run
+8 V
GND
IN
Description
59 (brown)
60
61 (blue)
Dosing controller NaClO
2
63 (brown)
64
62 (blue)
Dosing controller HCl
65
66
67
------------------------------
69 (brown)
70 (white)
68 (green)
Bypass water impeller counter
Summary of Contents for Oxiperm OCD-164
Page 2: ...2...
Page 247: ...Fran ais FR 247 4 crou filtre PVC gris...
Page 422: ...RU 422 10 10...
Page 431: ...RU 431 10 5 5 2 1 5 5 6 5 6 1 5 6 1 TM04 8202 4510 50 60 6 20 11 1D O2 O...
Page 432: ...RU 432 5 6 2 1 2 3 20 20 4 11 4 5 4 4 5 4 6 5 6 5 6 TM04 8203 4510 1 20 2 3 4 5 6...
Page 526: ...526...