Integration
333587D
83
Heat Data Exchange
E-Flo iQ Heat Data Exchange 18E224
Note: the “x” in the command value corresponds to the desired zone to be read.
Command Value
(base 10 decimal)
Name
Units/Format
Read/
Write
Min
Value
Max Value
0
AMZ Active Module Alarms
Bitfield
Read
0
2,147,483,647
1
AMZ Active Module Deviations
Bitfield
Read
0
2,147,483,647
2
AMZ Active Module Advisories
Bitfield
Read
0
2,147,483,647
3
I/O Daughter Board Active Module
Alarms
Bitfield
Read
0
2,147,483,647
4
I/O Daughter Board Active Module
Deviations
Bitfield
Read
0
2,147,483,647
5
I/O Daughter Board Active Module
Advisories
Bitfield
Read
0
2,147,483,647
6
Drum Sizes
Enum Number:
0: 20 Liters
1: 200 Liters
Read/
Write
0
1
7
Heat Idle Timeout
xx hours
Read/
Write
0
24
8
Line Voltage, Leg #1
xxx.x Volts
Read
0.0
400.0
9
Line Voltage, Leg #2
xxx.x Volts
Read
0.0
400.0
A
Line Voltage, Leg #3
xxx.x Volts
Read
0.0
400.0
Transition to Zones
z000
AMZ Active Zone #z Alarms
Bitfield
Read
0
2,147,483,647
z001
AMZ Active Zone #z Deviations
Bitfield
Read
0
2,147,483,647
z002
AMZ Active Zone #z Advisories
Bitfield
Read
0
2,147,483,647
z003
Zone #z Heat State
Bit Number:
0: Heat Zone Off
1: Heat Zone On
2. Heat Zone Warming up
3. Heat Zone At
Temperature
4. Heat Zone is Heat
Soaking
5. Heat Zone is in Setback
6. Heat Zone has a
Deviation
7. Heat Zone has an Alarm
Read
0
127
z004
Zone #z Actual Temperature
xx.x deg C
Read
0
100.0
z005
Zone #z Actual Current Usage
xx.xxx A
Read
0.000
25.000
z006
Zone #z Actual Duty Cycle
xxx.xx %
Read
0.00
100.00
z007
Zone #z Soak Time Remaining
xx seconds
Read
0
7200
z008
Zone #z Setpoint Temperature
xx.x deg C
Read/
Write
15
70.0
z009
Zone #z Setback Temperature
xx.x deg C
Read/
Write
15
70.0
z00A
Zone #z Heat Soak Time
xx.x minutes
Read/
Write
0
120
z00B
Zone #z Heat Enabled/ Installed State
boolean
Read/
Write
0
1