Integration
70
333587D
Job Cycle Timing Diagram
Timing recommendations:
• Use discrete signals when possible, especially for the Go signal. Use optional I/O Cable 128441 for discrete
signals.
• Use a 50 ms delay between bits.
Automation Control Ready in the following diagram represents:
• Pump is active
• No active alarms
• ADM is in Remote mode
Automation Inputs (E-Flo iQ Outputs)
Tag ID
Active
Pump
Pump Heartbeat To PLC
1
Automation Control Ready
2
System Active
3
+Pump PLC Lockout/Control Active
4
System Ready to dispense
8
Ƒ
Pre-charge / De-charge Active
9
Dispense In Process
10
Automation Outputs (E-Flo iQ Inputs)
ᶭ
System Enable/Remote Start Request
2
^System Disable Request
3
+Pump PLC Lockout/Control Request
4
+Desired Style Number Request (integer)
18
¸
Style Enable Request
5
¸
Go Signal Request (as required)
6
‡
¸
Dispense Complete Request
7
*
A job cycle can only be completed on the active pump
ᶭ
+
Can
only
be used through the fieldbus; and
must
be used to operate the system. Styles 17-99 can only be operated through the fieldbus.
Ƒ
Pre-charge
will only be active when there is a set-point stored in the display or passed over the CGM.
¸
‡
The dispense complete is optional. This bit summates the volume dispensed any time it is triggered. Dropping the style strobe will also summate the volume dispensed.
^
Disabling the pumps(s) is optional. Does not diable heat.
The signal source can be either discrete or fieldbus. Go to "Style Definitions", then navigate to "Style Integration Setup" screen define the source. However, it is highly
recommended to use the discrete signal for proper timing.
Notes:
Job Cycle Timing Diagram
Pre Job Cycle
Pre-charge/De-charge
Dispense 1
Dispense 2,3…
Post Job Cycle
Can be enabled at the same time.
CGM I/O Sequence
Function
Sequence Description
Pre-Job Cycle
1
Check that
Heartbeat
is toggling ON and OFF at 1Hz.
2
Check that
System Active
bit is ON.
If
System Active
bit is OFF, Turn ON
System Enable
bit.
3
Check that
Automation Control Ready
bit
is ON. Note: Active only when there are no active
alarms, the system is enabled and the system is in REMOTE mode.
If
Automation Control Ready
bit is ON, Turn ON
PLC Lockout
bit.
4
Check that
PLC Lockout
bit is ON.
If
PLC Lockout/Control
bit is ON
,
Enter desired
Style Number
(16bit integer).