2.4.1 HEIGHT DIFFERENCE BETWEEN INDOOR AND OUTDOOR UNIT
EXAMPLE FOR AEROGOR ECO INVERTER 10A
A) Outdoor unit is
above
Indoor unit
Maximum height difference is
X
m
.
Total pipe length distance can be maximum
Y
m
. In case of 7 m (
X
) height distance
between indoor and outdoor unit, horizontal pipe distance can be maximum 5 m (
Z
).
In that case is obligatory to integrate 1 siphon.
B) Outdoor unit is
below
Indoor unit
Maximum height difference is
X
m
.
Total pipe length distance can be maximum
Y
m
. In case of 5 m height distance
between indoor and outdoor unit, horizontal pipe distance can be maximum 7 m (
Z
).