27
3 ELECTRICAL
WIRING
3.1 AEROGOR
ECO
INVERTER
10A,
13A
AND
AEROGOR
POWER
EVI
INVERTER
15A,
18A
3.1.1 INDOOR UNIT
A
HEAT PUMP POWER SUPPLY (FUSE
– 20 A 1P C)
A*
HEAT PUMP POWER SUPPLY (FUSE
– 16 A 3P C) (POWER EVI INVERTER 15A,
18A)
B
INTERNAL ELECTRICAL HEATERS POWER SUPPLY (FUSE
– 3x10 A 1P C)
C
POWER SUPPLY FOR ADDITIONAL ELECTRICAL HEATER FOR DHW TANK
–
DEPENDING ON THE TYPE
D
INDOOR TO OUTDOOR POWER CONNECTION (230 V)
– 3x2,5
𝑚𝑚
2
D*
INDOOR TO OUTDOOR POWER CONNECTION (400 V)
– 5x2,5
𝑚𝑚
2
(POWER
EVI INVERTER 15 A, 18 A)
E
CONSTANT 230 V RESERVE
– MAX. LOAD 100 W
F
CIRCULATING PUMP
– HEATING CIRCUIT 1
G
CIRCULATING PUMP
– HEATING CIRCUIT 2
H
CIRCULATING PUMP FOR DHW (230 V on P3 during DHW operation)
I
ADDITIONAL ELECTRICAL HEATER FOR DHW TANK
J
DIVERTING VALVE
– DHW MODE WITH POWER
K
MODE SWITCHING SIGNAL (see page 65)