62
Possible settings
:
DC Variable Speed Pump (PWM Control)
- running according to parameter setting 6.11.2,
Condensing temperature control.
AC Pump
– No speed regulation, only high speed.
6.12.2 Speed Setting of Circulation Pump P0
Only value if parameter 6.11.1 is set to DC Variable Speed Pump (PWM Control).
Possible settings:
•
High Speed (default setting)
•
Middle Speed
•
Low Speed
It is not recommended to change the Circulate pump speed, before consulting with Gorenje
Engineers at HCS department.
6.12.3 Working Mode of Circulation Pump P0
Possible settings:
•
Interval working mode
– When the heat pump is not running (all the temperatures are
achieved), circulation pump P0 is running according to parameters
Pump Off Interval
for P0
and
Pump On Time for P0
. Default settings are OFF
– 10min, On – 1min.
•
ON constantly
•
OFF with compressor
– Circulation pump P0 works only when compressor is running.
6.12.4 Pump Off Interval for P0
Time for
Interval working mode
parameter where circulation pump P0 is deactivated.
Default setting is 10.
6.12.5 Pump On Time for P0
Time for
Interval working mode
parameter where circulation pump P0 is activated. Default
setting is 1.
6.12.6 Buffer Tank
Check this box if a Buffer tank is installed in the system.
6.12.7 P1 For Heating Operation
Check this box if circulation pump P1 will be used for Heating.
6.12.8 P1 For Cooling Operation
Check this box if circulation pump P1 will be used for Cooling.
6.12.9 P1 with High Temp. Demand
Check this box if you use a Room thermostat for Radiator heating for
heating
circuit 1
. Circulation pump P1 only works when the signal from a Room
thermostat is present. Room thermostat is connected to COM and TH
connectors with a
non-voltage
contact.
6.12.10 P2 for Heating Operation
Check this box if circulation pump P2 will be used for Heating.
Summary of Contents for Aerogor ECO COMPACT INVERTER 10A
Page 2: ......
Page 88: ...81 10 WIRING 10 1INDOOR UNIT ALL INVERTERS REFERS TO AS LINE OF HEAT PUMPS...
Page 89: ...82 INDOOR UNIT ALL INVERTERS...
Page 91: ...84 10 3OUTDOOR PCB ECO INVERTER...
Page 92: ...85 OUTDOOR PCB ECO INVERTER...
Page 93: ...86 10 4DRIVE FOR EEV ECO INVERTER 13A and ECO COMPACT INVERTER 13A...
Page 94: ...87 10 5OUTDOOR UNIT POWER EVI INVERTER 15A 18A...
Page 95: ...88 OUTDOOR UNIT POWER EVI INVERTER 15A 18A...
Page 96: ...89 10 6OUTDOOR UNIT DRIVE AEROGOR POWER EVI 15A 18A...