51
6.5.6 Reheating Restart
∆T Setting
For the second temperature mode for heating domestic water, this parameter is used to set
the DHW restart. The recommended setting is 5 °C.
Example:
Desired dome
stic hot water temperature is 45 °C, and the DHW restart setting is 5 °C. (45–
5=40).
H
eat pump will start reheating domestic water once it drops below 40 °C.
6.6 REDUCED
SETPOINT
6.6.1 Reduced Setpoint
Feature on/off.
A check in the box means that the feature is on.
The feature lowers water temperature by the set value for both heating circuits in the set
time. The main purpose is to lower room temperature at night.
6.6.2 Temp. Drop/Rise
The space heating water temperature drop/rise is set for both heating circuits.
6.6.3 Timer for Reduced Setpoint Function
Timer for feature activation is set!
If the fields are green, domestic water heating is on.
If the fields are grey, it means the heat pump is not
heating domestic water.