4.1.5.15 Setting Feed-in Grid Percentage
WAIT
KW
KW
KW
KW
KW
KWh
INVERTER EXPERT
EOUT
FED
%
Figure 53 Feed-in Grid Percentage Setting
FED refers to feed-in grid percetage. The system is will not feed any energy into the grid if the FED
value is set to 0%. The system is free to export to the grid if the FED setting to 100%.If the FED is set
to 10%, then the largest power allowed to be fed into the grid is 3600W*10%=360W.
The default FED value is 100%, please press ”OK” to modify it.
4.1.5.16 Restore to Factory Setting
Press “
▲
”to enter setting interface as shown in Figure 54.
WAIT
KW
KW
KW
KW
KW
KWh
INVERTER EXPERT
EOUT
RST
Figure 54 Restore to Factory Setting
RST refers to restore to the factory setting. Please input the value ”1111” if you need to restore the
system into the initial setting out of factory. Press “ESC” to quit from the setting page and enter the
display menu.
Note:The setting should be operated when the Powervortex3700TL is under “wait” status, otherwise
the ”E05”error might occur to the system.