GBESS 2.4_4.8KWH system user manual
31
code to modify. Press “OK” to finish the setting and you will enter the setting interface as shown in
Figure 37.
4.1.5.4 Setting Battery Charging Cut-off Voltage
WAIT
KW
KW
KW
KW
KW
KWh
INVERTER EXPERT
EOUT
BVH
V
Figure 37 Battery charging cut-off voltage setting
BVH refers to battery charging cut-off voltage. The BVH setting range is 40V-60V, the default value is
54V.Please set the voltage according to the battery recommended value for different battery types.
Press “OK” to modify setting on this parameter. Make sure the BVH value input here is higher than
the BVL value setting Section 4.1.5.5. Press “OK” to finish this setting and you will enter the setting
interface as shown in Figure 38.
4.1.5.5 Setting Battery Discharging Cut-off Voltage
WAIT
KW
KW
KW
KW
KW
KWh
INVERTER EXPERT
EOUT
BVL
V
Figure 38 Battery Discharging Cut-off Voltage Setting
BVL refers to battery discharging cut-off voltage with setting range from 40V to 60V. Default BVL
value is 46V for lithium battery and 47V for lead-acid battery. Please set the voltage according to the
battery recommended value for different battery types.