Global Power Technologies
3-13
5120
Symptom
Probable Cause
Remedy and Procedure
Low output power or low
voltage.
Incorrect set-up voltage for
site temperature.
Determine required V
set
for present conditions. Section 2.6.1.
Insufficient cooling around
fins.
Clear fins of any debris.
Dirty fuel filter
Drain regulator sediment bowl.
Section 3.2.2.1.
Change filter. Section 3.2.2.2.
Orifice plugged.
Change orifice. Section 3.2.2.3.
SO valve malfunctioning.
Check SO valve. Section 3.2.6
Incorrect air supply.
Adjust air supply. Section 2.6.4.
Clean air screen. Section 3.2.3
Incorrect fuel adjustment.
Adjust fuel regulator. Section 2.6.5
Limiter Converter needs
adjusting or repair.
Check switch settings.
Check output voltage adjustment Pot.
Power unit faulty.
Check momentary open circuit voltage,
section 3.2.1
Output power or voltage
is too high.
Incorrect fuel adjustment.
Lower fuel pressure. Section 2.6.5
Incorrect Limiter Converter
adjustment.
Re-adjust the output voltage adjust
-
ment Pot.
Summary of Contents for 5060
Page 2: ......
Page 4: ......
Page 6: ... ...
Page 8: ......
Page 10: ...Global Power Technologies 1 2 5120 ...
Page 15: ...Global Power Technologies 1 7 5120 ...
Page 27: ...Global Power Technologies 2 12 5120 Figure 13 Wiring Diagram 5120 TEG ...
Page 35: ...Global Power Technologies 3 8 5120 Figure 18 Burner Assembly ...
Page 47: ...Global Power Technologies 3 20 5120 ...
Page 50: ...Global Power Technologies 4 3 5120 Figure 26 220 Watt L C Connection and Adjustment Details ...
Page 51: ...Global Power Technologies 4 4 5120 ...
Page 55: ...Global Power Technologies 5 4 5120 Figure 30 Cathodic Protection System Parts Identification ...
Page 57: ...Global Power Technologies 5 6 5120 ...
Page 63: ...Global Power Technologies 6 6 5120 Figure 33 Exhaust Stack Removal ...
Page 75: ...Global Power Technologies 7 2 5120 7 2 Physical Dimensions Figure 42 Physical Description ...