UFO-NT
22
Push And Go
10 Push And Go
WARNING
Danger of injury due to crushing and shearing!
X
During an activated Push And Go function door handles can form potential danger points.
à
The Push And Go function allows activation of the drive without contact sensors being used.
à
When the Push And Go function is set, the drive opens the door automatically as soon as the door leaf is
moved manually out of the closed position.
à
The opening angle for use of the automatic opening functions can be adjusted (1°–20°).
à
For comfortable use, the opening time should not be set to the minimum value.
An opening angle that is set too small can result in undesired automatic opening of the door.
The door must be labeled in accordance with DIN 18650 when using this function.
à
To operate the DPS DPS see chapter 27.4 "DPS (DPS)".
à
To operate the service terminal ST220 see chapter 27.1 "Service terminal ST220".
The state of the drive to which the ST220 is connected is displayed.
X
Press the
button.
X
Select "Active leaf para" or "Passive leaf para" using the
or
key and press the
key.
For further settings, see the descriptions below.
à
Set the parameters with:
à
DPS:
Set
pU
to the desired opening range (1-20) to start the automatic opening function
or
set
pU
to
0 0
to disable the function.
Set
op
to the desired hold-open time with "Push And Go" (0 – 60 s).
à
ST220: Use the or key to set the "Movement parameters", "Push And Go" to the opening range (1-20) to
start the automatic opening function or set "Push And Go" to 0 to disable the function.
Set the "Movement parameters", "Hold-open times", "Push And Go" to the desired hold-open time
(0 – 60 s).
11 Configurable inputs
à
Various special functions are assigned to the configurable inputs PE1, PE2 and PE3, see 27 ""Service menu"".
The contact type required for the desired function is specified in chapter 27.5 ""Service menu DPS"", or chapter
à
The configurable input PE1 is a pure binary input which is only suitable for the connection of NO or NC con-
tacts - not however for the connection of the analogue programme switch MPS.
à
Configurable inputs PE2 and PE3 are analogue inputs which are suitable for the connection of NO or NC con-
tacts as well as for the connection of the analogue programme switch MPS, see chapter 16 ""Mode of opera-
à
To operate the DPS DPS see chapter 27.4 ""DPS (DPS)"".
à
To operate the service terminal ST220 see chapter 27.1 ""Service terminal ST220"".
The state of the drive to which the ST220 is connected is displayed.
X
Press the
button.
X
Select "Active leaf para" or "Passive leaf para" using the
or
key and press the
key.
X
Select "Signals" "Input signals" and press the
key.
For further settings see the description below.
à
Set the parameters with:
à
DPS: Set
e1
,
e2
or
e3
to the desired function.
à
ST220: Set "PE1", "PE1 function", "PE2", "PE2 function" or "PE3", "PE3 function" to the desired function.
11.1 MPS
See chapter 16.1 "Programme switch", "Mechanical programme switch (MPS)".
An MPS can only be connected to PE2 and PE3.