3. INSTALLATION
3.1 POSITIONING
The 5500 Steam Humidifier has been designed for wall
mounting and since it is an electrode steam humidifier,
should be placed close to the point where the steam will be
ducted to minimize the steam hose length (and the amount
of condensate).
IMPORTANT:
Certain minimum clearances must be
maintained around the unit for safety and maintenance.
(See Fig. 3.a. and Table 3.a)
IMPORTANT:
DO NOT introduce steam into duct that has
interior insulation.
E
A
B
C
D
F
Fig. 3.a
Item
Description
Inches
mm
A
Side
6
150
B
Top
6
150
C
Side
6
150
D
Bottom
6
150
E
Front
24
600
F
Angularity
0.2
0
max
Tab. 3.a
3.2 MOUNTING / DIMENSIONS AND WEIGHT
Removing the Front Cover
The front cover is fastened by two tabs at the top and one
screw located at the bottom center of the unit. Use a Phillips
head screwdriver to remove the screw (Fig. 3.b.), then swing
and lift cover away from the back part of the unit. Return it in
reverse order. Be careful not to over-tighten the screw.
See Table 3.b for dimensions and weights.
A
B
C
Fig. 3.b
Item
Description
Inches
mm
A
Width
13.0
345
B
Depth
8.25
206
C
Height
21.0
533
Pounds
Kilos
Empty weight
16
7.3
Weight with water
24
10.9
Shipping weight
26
11.8
Tab. 3.b
Summary of Contents for GeneralAire 5500
Page 6: ...6...
Page 37: ...31 Form No 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 ENG...
Page 38: ...32 NOTES...
Page 39: ...33 Form No 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 ENG...
Page 41: ...35 Form No 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 ENG...
Page 42: ...36...
Page 43: ...37 Form No 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 ENG Mode d emploi...
Page 48: ...42...
Page 79: ...31 Formulaire no 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 FRE...
Page 81: ...33 Formulaire no 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 FRE NOTES...