Side Installation Horizontal Duct
Height >8”
1/3 Height
Fig. 3.f
Side Installation Vertical Duct
=
=
8” Min
Fig. 3.g
Important:
DO NOT introduce steam
into a duct that has interior insulation.
Steam Nozzle (optional)
The optional steam nozzle (See Fig. 3.h. and Table 3.d.) can be
used for horizontal surface installations (i.e. the bottom of a
horizontal duct) or vertical surface installations (See Fig. 3.i.).
A condensate hose is required. To install the steam nozzle,
cut a 2-1/2” round hole in the duct. Apply silicone sealant to
the mounting plate and insert the nozzle through the hole
and secure with sheet metal screws. Connect the steam and
condensate hoses using the hose clamps supplied. Select
an accessible location on the duct, allowing at least 36” of
straight duct (no elbows or obstructions) after the point where
the steam nozzle will be installed and the clearances can be
maintained as per the following drawings.
F
H
G
I
C
A
B
B
D
A
A
E
B
A
Steam Inlet
Condensate drain
Apply silicone
sealant to this face
Fig. 3.h
Inches
mm
A
1.24”
31.5 mm
B
1.96”
50 mm
C
2.20”
56 mm
F
2.26”
57.5 mm
E
3.93”
100 mm
F
0 0.31”
0 8 mm
G
0 0.86”
0 22 mm
H
0 1.18 “
0 30 mm
I
0.87”
22 mm
Tab. 3.d
Summary of Contents for GeneralAire 5500
Page 6: ...6...
Page 37: ...31 Form No 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 ENG...
Page 38: ...32 NOTES...
Page 39: ...33 Form No 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 ENG...
Page 41: ...35 Form No 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 ENG...
Page 42: ...36...
Page 43: ...37 Form No 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 ENG Mode d emploi...
Page 48: ...42...
Page 79: ...31 Formulaire no 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 FRE...
Page 81: ...33 Formulaire no 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 FRE NOTES...