8. TECHNICAL SPECIFICATIONS
SPECIFICATION
DESCRIPTION
NOTES
Capacity / VAC / kW
4.9 lbs/hr (2.2 kg/h) / 115 VAC 1-phase 50-60 Hz / 1.86 kW
9.9 lbs/hr (4.5 kg/h) / 230 VAC 1-phase 50-60 Hz / 4.05 kW
Steam pressure
3.81 in WC / 950 Pa (.137 PSI)
Dimensions (inches / mm)
21” H x 13” W x 8.25” D / 533mm H x 343mm W x 210mm D
Weight empty/packaged/installed
with water (pounds / kilograms)
16 / 26 / 24 lbs. (7.3 / 12 / 11 kg)
IP class
IP20
Electrode power cables
AWG12
Power relays (amps)
2 x 30
On board
Ground connection
Screw
Input water type
Potable water
No demineralized or softened water
Conductivity range (microSiemens) 125-1250 µS/cm
Water fill connection
1/4” O.D. Compression
Adapter to 3/4” BSP
Water fill - instant flow
0.09 – 0.16 gpm (0.35 – 0.60 l/min)
Drain hose
¾” ID x 10 ft. drain hose supplied (19 mm ID)
From bottom of unit
Drain water temp F / C
< 140°F / < 60°C
Drain tempering device
Drain flow
Initial Max drain rate using ¼” OD supply tubing and full cylinder – approx 1.1 gallons for first 15
seconds of drain cycle (~4.4 gpm (13.2 l/min))
Initial Max drain rate using hose with ¾” BSP fitting – 6.3 gpm (23.8 l/min)
Average drain rate – 3.8 gpm (14.4 l/min) (measured over a one minute period starting with full
cylinder)
Serial communication
DS485
Unit voltages
Primary 115 / 230 Volts AC / Control Wiring 12 Volts DC
Electrical requirements
Require AWG12 external power wires to electrical panel with a dedicated 20A
Max output
28.5 GPD max. If unit is not config.d (section 4.4) then default setting from factory is 20.9 GPD at
230V
Steam hose
6‘ blue steam hose ID 7/8” (22mm), OD 1 ¼“ (30mm), (GFI #7525)
8“ Steam manifold (standard)
8“ steam manifold supplied with duct mounting kit
OPTIONAL
GF-12502 air pressure switch
Actuated by positive, negative or differential pressure of .05“ W. C. or more (GFI #7021)
RMB35 room steam kit
230V Includes room blower assembly and grille package (GFI #7660)
Steam nozzle
Optional accessory can be used for bottom duct installation (GFI #7500 / CGF#GF-20-1)
GF-DPO30KIT
Optional accessory 12" length steam distribution manifold (GFI #7521)
GF-DP045KIT
Optional accessory 17.5" length steam distribution manifold (GFI #7522)
FIELD SUPPLIED
Copper tubing
OD 3/4" to fit ID of blue steam hose
Inline pre-filter
Any activated carbon element and particulate element rated for 5 micron or less and min 25 GPM
Condensate pump
3 gpm min. flow at 0 head and 1 gallon reservoir min. The technician is responsible for selecting the
appropriate condensate pump for the installation
Tab. 8.a
Summary of Contents for GeneralAire 5500
Page 6: ...6...
Page 37: ...31 Form No 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 ENG...
Page 38: ...32 NOTES...
Page 39: ...33 Form No 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 ENG...
Page 41: ...35 Form No 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 ENG...
Page 42: ...36...
Page 43: ...37 Form No 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 ENG Mode d emploi...
Page 48: ...42...
Page 79: ...31 Formulaire no 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 FRE...
Page 81: ...33 Formulaire no 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 FRE NOTES...