10
10
1/3 height
H > 8”
Airflow
1000 cfm. min
Airflow
1000 cfm. min
Airflow
min 8” 200 mm
=
=
Airflow
1000 cfm min.
24” min
Upstream
36” min
Downstream
=
=
min 8” 200 mm
Bottom Installation
Horizontal Duct
Side Installation
Horizontal Duct
Side Installation
Vertical Duct
Fig. 3.i
3.7 STEAM MANIFOLD (12” & 17.5” OPTIONS AVAILABLE)
For certain applications, a longer steam manifold may be required. Select an accessible location on the duct, allowing at least
36” of straight duct (no elbows or obstructions) after the point where the steam manifold will be installed and the clearances can
be maintained as per the following drawings.
To mount the steam manifold, cut or drill a 2-1/2” hole in the duct (See Fig. 3.i). Apply caulk to the mounting plate of the manifold.
Attach the steam manifold to the duct using (4) #10 sheet metal screws (supplied). Install end bracket to maintain correct slope.
IMPORTANT:
Allow 5 feet (1-1/2 m) of straight return duct downstream of the distributor pipe or nozzle for absorption of
the steam. Always allow 3 feet (0.9 m) of straight supply duct upstream of the distributor manifold or nozzle for evaporation of
the steam. Turbulent air flow may require longer lengths.
The return condensate hose from the steam nozzle / steam manifold must be trapped. Coil the hose into a vertical loop and
secure it below the steam nozzle / steam manifold. This trap prevents steam from being released into the cabinet. The end of the
¼” ID hose may be run through the knockout at the top of the humidifier and inserted into the hole located on top of the fill cup.
A
B
Y
X
dimensions in mm (inches)
use the manifold support bracket, supplied, to ensure
the 2° slope due to the shape of the flange
22 (0.87”)
10 (0.39”)
58 (2.28”)
35 (1.38”)
68 (2.68”)
30 (1.18”)
10 (0.39”)
68 (2.68”)
45 (1.77”)
77 (3.03”)
Optional stainless-steel steam manifold
USA: 25-10 12” or 25-11 17.5” Canada: GF-DP030 Kit 12” or GF-DP045 Kit 17.5”
condensate drain
flange gasket
steam inlet
B
Y
hole in wall
screws max. dia. “M5”
X
A
X
°2
fasten the manifold support bracket
L (
see table on above)
Fig. 3.j
Summary of Contents for GeneralAire 5500
Page 6: ...6...
Page 37: ...31 Form No 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 ENG...
Page 38: ...32 NOTES...
Page 39: ...33 Form No 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 ENG...
Page 41: ...35 Form No 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 ENG...
Page 42: ...36...
Page 43: ...37 Form No 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 ENG Mode d emploi...
Page 48: ...42...
Page 79: ...31 Formulaire no 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 FRE...
Page 81: ...33 Formulaire no 5500 32 Rev C Code 0700092EN REV 3 2 04APR2022 FRE NOTES...