IST-1408.PA01.02 - Dis.0534045
CE408P / User Manual
Pag. 35/41
GECA S.r.l. - Via E. Fermi, 98 25064 GUSSAGO (BS) - Tel. 030 3730218 - Fax 030 3730228
APPENDIX
CE408 Technical Specifications
AC power supply and frequency
90 to 264 V AC / 47 to 63 Hz
AC Maximum consumption
(1)
1A at 230V AC
Max current delivered by the power supply
2,7 A at 27,6V DC
Power consumption at 24VDC
(2)
30 W Max
Analog Input 4 to 20 mA (Linear)
8 maximum, of which n.4 factory installed, others are
expandable to 8 with expansion board ES404
Analog Input - Load resistance
100 Ohms
Max.Current/Voltage available per imput
100 mA / 24 VDC (–10/+15%)
Internal Output relay
(
with voltage free changeover contacts
)
9 maximum, of which n.5 factory installed,
expandable to 9 with the expansion board ES414
Nominal load of relay (
SPDT contact on each relay
) 250 VAC – 2 A or 30 VDC – 2 A resistive load.
Logic inputs
1 (for NA or NO dry contacts)
SD card accepted
SD e SDHC max 32Gb
SDXC formatted by PC with FAT32 (max 32Gb).
Display
monochrome LCD graphical display with backlight
Optical indications
n. 3 LEDs (Yellow, Green and Red)
Acoustic indications
Internal Buzzer
Keyboard
8 keys
Backup battery (
optional
)
(3)
n. 2 Pb 12VDC / 1.3Ah (connected in series)
Battery operating time (
with 4 sensors
)
(4)
About 80 minutes
Battery operating time (
with 8 sensors
)
(4)
About 60 minutes
Temperature of use (
with batteries
) / Humidity
+5 to +40 °C / 5 to 95% relative humidity
Dimensions
CE408P 280 x 230 x 145 mm
Weight (
without the batteries
)
CE408P about 2.8 Kg
(1)
With all the 8 sensors connected and 9 relays activated.
(2)
Max power absorption at 27.6VDC supplied from the power supply (with 8 sensors).
(3)
The batteries are not included. If it were required more autonomy, can be used 2 Pb Batteries 12V 3Ah or 7Ah connected in series,
but due to their size, they should be installed in an external housing. Autonomy, with 8 sensors becomes: about 2 hours with 3Ah
batteries (each sensor in less increases the autonomy of approx 10 min) and about 5 hours with the 7Ah (each sensor in less
increases the autonomy of approx 30min .).
(4)
Each sensor in less, increases the autonomy of approx 5 minutes (eg, with 6 sensors, the range increases to 10 min.=70 min.).
TABLE with summary of Fault and Alarm messages.
CONDITION
Displaying
Yellow
LED
Green
LED
RED
LED
Buzzer
(if configured
Sensor not Configured
- - - -
Fixed ON
Sensor (<1mA) or Zone in Fault
FAULT
Fixed ON
Fixed ON
Activated
Sensor or Zone returned from a Fault, but with
output relay latched.
NORM
(Blinking)
Short blinking
(2)
Fixed ON
Sensor operating normally
NORM
Fixed ON
Battery Operation - (with graphical indication,
from Full Charge up to Discharge)
÷
Blinking
(1)
Batteries Fault
Blinking
(1)
Rapid blinking
(3)
Fixed ON
Sensor or Zone or Logic Input, in Alarm 1
AL 1
Fixed ON
Blinking
Sensor or Zone or Logic Input, in Alarm 2
AL 2
Fixed ON
Blinking
Sensor or Zone in Alarm 3
AL 3
Fixed ON
Fixed ON
Activated
Sensor or zone or logic input, with Alarm 3
returned to normal, but with relay output latched.
NORM
(Blinking)
Fixed ON
Short
blinking
(2)
Sensor (>24mA) over the Full Scale
F.S.
Fixed ON
Fixed ON
Fixed ON
(1)
Blinking = 1sec ON / 1sec OFF /
(2)
Short blinking = 0,1sec ON / 1sec OFF /
(3)
Rapid blinking = 0,1sec ON / 0,1sec OFF
DISPLAY MESSAGE
EXPLICATION
See page
WRONG PASSWORD
Was entered a wrong code level.
27
FIRMWARE CORRUPTED
The CE408P is not able to start, Firmware incomplete or missing
30
UPDATE FAILED
The CE408P is not able to update the firmware from SD-Card
33