Display – Initial Screens
The
CE408P
when powered, for 5 seconds shows the model name and
firmware version. -----------------------------------------------------------------------
This information shall be accessible also in the menu
Settings
General
Info.
For more information read the chapter
Settings
.
Only at first power (and only then)
will be asked to choose
your language and to indicate if the battery is present. Use the
key
and
to scroll through the languages and pressing
the key
ENTER
to confirm the choice. ----------------------------------------------
From this screen, you cannot go out without being made a choice.
If necessary, these choices can be changed.
Please see forward
Settings
General
and
Service
Battery
.
After starts a decreasing count of 60 seconds, the time required to boot
the central unit, and allow the sensor to stabilize (
preheating time
). ----
After the preheating time, appears the
Main screen
that the control unit
displays in normal operation. The date is shown in the top row, the first 6
sensors (
with the measured concentration and its state
) and in the last
line, the battery status of charge (
if installed
) and the presence of mains
power:-------------------------------------------------------------------------------------
Symbols used to indicate the status of the battery (if installed):
= Full charge
= Half charge.
= Low charge
= Discharge
Flashing = Fault.
Symbols used to indicate the presence of mains power:
= mains operation (
is absent, when the power is by the batteries
).
If the control unit, had lost the date and time, due to a malfunction or discharge of the clock
backup battery, screen will be displayed for entering updated values (
however, will assure
the normal unit operation
). By changing these parameters, see below, the section
SETTINGS
DATE and TIME
The status of a sensor, which appears on the main screen, may be:
•
“
- - - -
“
=
Sensor not Configured
.
•
FAULT
=
input current is less
than 1mA.
•
NORM
. =
Normal
There is no gas and there are no active alarms. The text blinks when
relay output is latched (Sensor or Zone).
•
AL.1
=
Alarm 1
.
The
first
alarm
threshold has been exceeded.
•
AL.2
=
Alarm 2
.
The second alarm
threshold has been exceeded.
•
AL.3
=
Alarm 3
.
The
third
alarm
threshold has been exceeded.
•
F.S.
=
Full Scale
.
Current > 24 mA. The gas concentration has exceeded the Sensor
range.
LINGUA-LANGUAGE
LANGUE
1 ITALIANO
2 ENGLISH
3 FRANÇAIS
PRESENCE
BATTERY
1 NO
2 YES
WAIT
60
12:00 fri 15/11/2013
1) 2% LEL NORM
2)10.2 ppm AL.1
3) 300 ppm AL.3
4) - - - -
5) - - - -
6) - - - -
¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯ ¯
CE408
ver.
1.00