If this procedure is correct, a window notifies you that the operation has
been successful. -----------------------------------------------------------------------
Then the screen returns to the selection of the type of configuration.
Configuring a GENERIC SENSOR
: to proceed with the configuration,
press
ENTER
on its line.
Then, in the corresponding screen, with
and
key and pressing
ENTER
you can choose the number of the sensor to be configured. ---------
Then the model is set as
GENERIC
and it is possible, move on to setting
of all parameters. The parameters should be inserted similarly to the
configuration of the Preconfigured Sensor. In this case, however, you can
also change the following items:
Description of the items relating to the Generic Sensor:
TYPO:
This item indicates the gas that the sensor will detect. You can choose between Flammab.
(
Flammable
), Toxic, Vital (
e.g. Oxygen
) and Asphixian. (
e.g. CO
2
is asphyxiating
).
GAS:
This entry indicates the name of the gas to the sensor has been calibrated. You can choose
between METHANE, LPG, PETROL (
Petrol vapours
), HYDROGEN, VARIOUS (
various gases
),
STYRENE, ACETYLENE, AMMONIA,
CO
,
CO
2
,
H
2
S
,
NO
,
NO
2
,
SO
2
,
HCN,
OXYGEN,
CL
2
e
HCL
.
UoM:
This item indicates the
unit of measurement
of the concentration detected by the sensor.
You can choose between
%LEL
(
Lower Explosive Limit
),
%vol
(
Volume
),
ppm
(
parts per million
),
ppb
(
parts per billion
) and
°C
(
temperature in degrees Celsius
).
RANGE:
This item shows the sensor's
full scale
. It consists of four digits and you can also set the
decimal point. The numbers allowed, ranging from a minimum of
1
,
0.1
or
0.01
up to a
maximum of
9999
,
99.9
or
9.99
. Other values or combinations are not accepted and, if
entered, will display the previous value.
With the
and
you can move from one digit to another, while with
e
you can
change the value.
The configurations of the full scale that use a number of digits less than 4 must be preceded by
a
space
.
Example
: To obtain a
Range
of
90
to enter
space
,
space
,
9
,
0
. Instead, the values
space
,
9
,
0
,
space or
9
,
0
,
space
,
space
, will not be accepted.
COPY (Level 2)
: This item allows you to copy the configuration of a
sensor to another sensor or group of sensors.
To copy a sensor, press
ENTER
on its item.
Then you enter the screen where pressing
ENTER
and using
and
keys, you can choose which sensor to copy. -----------------------------------
After pressing
ENTER
again to confirm, you can use the
and
key,
choose whether to copy on a single sensor or in a group.-------------------
The first line acts on a single sensor. Pressing
ENTER
on the first line, will
be highlighted the number of the sensor.
Then press
and
keys, to select the desired number, then press
ENTER
will appear the confirmation window.
PRECONFIG. SENS.
SENSOR
N. 1
CONFIGURED
GENERIC SENSOR
SENSOR N.
1
COPY
SENSOR N.
1
COPY
SENSOR N.
1
ON SENSOR N.
FROM N. TO N.