PRES. BAT.
(Presence Battery):
•
When set
NO
, the battery is not present
. In the main screen, the icon in the bottom left will be
absent and if there is no mains power, the control panel will shut down.
•
When set
YES
, indicating the presence of the battery.
In the main screen, the icon in the bottom
left indicates the charge status of the battery according to the following scheme:
o
: Battery full charge. The battery voltage is greater than 26.5 VDC.
o
: Battery partially charges. The battery voltage is between 24 VDC and 26.5 VDC.
o
: Battery half charge. The battery voltage is between 24 VDC and 22 VDC.
o
: Battery discharge. The battery voltage is 20.7 VDC and 22 VDC.
o
(
Flashing
): Battery Fault. The battery voltage is below 20.7 VDC or greater than 28 VDC. The
battery is considered faulty and is no longer charged. So you will need to replace the two
batteries.
TEST BAT.
(
Test Battery
):
•
When set
YES
, it is activated or indicates that the test is in progress. The test takes about a
minute, and checks, with a load, the proper functioning of the battery. If during the test, the
battery voltage drops below 20.7 VDC, is reported as a
Fault
(
see above
), and the battery will
not be recharged.
The test will not be activated in the absence of mains or battery
.
•
When set
NO
, the test indicates that you disable or do not on the battery test.
When the Battery Test is active, on the power board, placed in the base of the housing, its
LED will light, (
BAT TEST ON
). Consider that the two power resistors (load) will heat up
during the test.
SENSORS STATUS (Level 2)
: This item allows you to view the
current value of the sensors connected to the analog inputs.
Press
ENTER
on the relevant item. You will see input sensors value, in
current (mA), using
and
key, to scroll through the sensors. ----
To go back, press
ESC
.
If the board ES404, had not been installed, the displayed values of the corresponding inputs,
should not be considered, normally remain at zero.
Consider that, for all the values shown, the two digits after the decimal point may fluctuate.
START-UP (Level 3)
:
This submenu is not accessible, is reserved for the factory test
.
SD CARD
In this submenu you can manage the SD card after it has
been inserted in its slot. The card slot is on the circuit, in the housing
cover. -------------------------------------------------------------------------------------
The SD Card compatible, are
SD
and
SDHC
cards
up to
32GB
. The
SDXC
card must be formatted with
FAT32
(max
32GB). Normally, the unit accepts all SD Card, it is advisable
to use those qualified producers.
UPDATE FIRMWA. (Level 2)
: This item allows you to
update the firmware
of the unit, using an
update file previously saved on an SD Card The file must be downloaded from our website
"www.cavagnaindustrie.com" in
DOWNLOAD> SOFTWARE> Firmware Update CE408
and then
follow the instructions.
Pressing
ENTER
on the relevant item, you will see what to do before you
start the upgrade procedure.
First, move the jumper JP3 in position "
CLOSED
" and then insert
the SD card into its slot (
see below figure 6
).
Then press
ENTER
to start the update, or press
ESC
to go back.-------------
SENSORS STATUS
1) 04.00 mA
2) 05,23 mA
3) 04,05 mA
4) 12,38 mA
5) 12,00 mA
6) 11,58 mA
SD CARD
1 UPDATE FIRMWA.
UPDATE FIRMWARE
INSERT IN THE
CONTROL UNIT
THE JUMPER JP3
THE SD CARD
AND PRESS ENTER