IST-1408.PA01.02 - Dis.0534045
CE408P / User Manual
Pag. 20/41
GECA S.r.l. - Via E. Fermi, 98 25064 GUSSAGO (BS) - Tel. 030 3730218 - Fax 030 3730228
Description of the items relating to the outputs:
OUTPUT N.:
Indicates the number of the output (
relay
). The configurable outputs ranging from 1-9.
The output of
0
indicates that there is no output associated with that alarm level.
If the output boards are not properly connected or mounted, for safety, the
corresponding outputs cannot be configured.
•
If the board ES414 is not connected to the terminal
OUT 1-4
outputs will only be available
from 5 to 9.
•
If the board ES414 is not connected to the terminal
OUT 5-8
outputs will only be available
from 1 to 4 and 9.
•
If it was not connected any board ES414, the only output available is 9.
•
The outputs have to configure in a unique way. So, if you were choosing the same output for
different alarm levels will be considered valid, only the configuration of the higher alarm. You
cannot choose the same output for a level of alarm and fault
SILENCEABLE:
Indicates that the output is disabled, the
Silence time
, when
RESET
is performed.
This function can be used for the outputs connected to audible warning devices
SILENCE T.:
Indicates the
Silence time
(adjustable from 0 to 300 seconds), so Silenceable output
is cancelled by
RESET
.
DELAY
ON
:
DELAY
ON
is the relay delay (Adjustable from 0 to 300 seconds) associated with an
alarm threshold.
If the alarm type was selected as
PARKING EN
and you were programming the output on the
threshold 3, this delay can only be set from 60 to 300 seconds.
DELAY OFF/TIME ON:
The first item
DELAY
OFF
(adjustable from 0 to 300 seconds), is the
relay’s delay, to return to normal status, when it ends the alarm condition. The second item,
TIME ON
(adjustable from 0 to 300 seconds) can only be used to stop the alarm output after
a preset time, even if the sensor remains above the alarm threshold set. (It
can be used to
activate devices that cannot be powered on or to send a pulse to a phone-dialer
).
The two functions
HISTER.OFF
and
TIME ON
, cannot be used together, or with the
SAVE
function.
For safety, if the delay is set other than zero, the parameter stores will be
automatically changed to
NO
.
POS.LOGIC:
Indicates that the output operation is in
POSITIVE LOGIC
or the relay is normally
activated, so, in case of failure automatically moves into the position of the alarm, and then
the NC contact becomes NO
LATCHED:
Indicates that the relay remains in alarm, even if the sensor back below the alarm set.
To bring it back into the normal,
RESET
must be performer.
The function
LATCHED
, cannot be used simultaneously with
DELAY OFF
or
TIME ON
. For
safety, if the parameter
LATCHED
, was set
YES
, the parameters
DELAY OFF
and
TIME ON
,
will be automatically set to Zero
At the end of the screen is written
SAVE
to save the configuration entered. Pressing
ENTER
the
confirmation window will appear. Press again
ENTER
to confirm, or press
ESC
to go back and make
changes.
Only for double sensors, TS255 series, at the end of the screen, the message
CONTINUE
appears. Because in this case, must be programmed two consecutive sensors. Only after the
second configuration, you can save the configuration entered.
If the set thresholds were in contrast with the criteria for this type of alarm
set, or if it had selected the same output for one of the alarm levels and
the Fault, a warning message will appear.---------------------------------------
Then the screen returns to the configuration of the sensor
PRECONFIG. SENS.
ERROR
CONFIGURATION
CONTROL
PARAMETERS