Installation
2-5
January 2008
Wiring The Remote
Transmitter - J6
Terminal block J6 contains the analog signal and loop power
connections for the remote transmitter. To wire the transmitter,
complete the following steps:
1.
Connect the XDP to the transmitter as follows:
Note:
Refer to the transmitter manual for details on wiring the
transmitter’s terminal block(s).
a.
Connect pin #1 to the positive terminal of the analog output
from the transmitter.
b.
Connect pin #2 to the +24 VDC loop power input on the
transmitter.
c.
Connect pin #3 to the return connection of the analog output
from the transmitter.
Proceed to the next section to continue wiring the XDP.
Wiring The XDP Alarm
Relays - J3
Terminal block J3 contains connections for the XDP alarm relays. To
wire these alarms, complete the following steps:
Note:
A
failsafe
alarm is wired to the normally-closed (NC)
contacts, while a
non-failsafe
alarm is wired to the normally-
open (NO) contacts.
1.
Connect the
Normal
alarm as follows (this alarm is factory-
configured for
failsafe
operation):
a.
Connect pin #1 (NC) to the alarm device input.
b.
Connect pin #2 (C) to the alarm device return.
c.
Pin #3 (NO) is not used for fail-safe operation
2.
Connect the
XDP Fault
alarm as follows (this alarm is factory-
configured for
failsafe
operation):
a.
Connect pin #4 (NC) to the alarm device input.
b.
Connect pin #5 (C) to the alarm device return.
c.
Pin #6 (NO) is not used for fail-safe operation
Summary of Contents for XDP-H2
Page 3: ...Chapter 1 ...
Page 9: ...Chapter 2 ...
Page 20: ...Chapter 3 ...
Page 28: ...Chapter 4 ...
Page 55: ...Chapter 5 ...
Page 76: ...Chapter 6 ...
Page 80: ...Appendix A ...
Page 81: ...CE Mark Compliance Introduction A 1 EMC Compliance A 1 LVD Compliance A 1 ...
Page 83: ...Appendix B ...
Page 87: ...Appendix C ...