Masoneilan SVI II AP Digital Positioner Quick Start Guide
=
|
31
© 2015 General Electric Company. All rights reserved
.
3. Set rod-ends and brackets to stroke and size of actuator. The default setting is a
4.00” stroke. Other stroke settings are as in Figure 15.
Figure 15
Stroke Settings
4. Mount take-off bracket to stem block at angle which keeps turnbuckle assembly
parallel to stem (Figure 16) using:
a. For top: two plain 5/16 flat washers, helical spring washer 5/16, two hex nuts 5/
16-18 regular.
b. For bottom: hex nut regular 1/4-20 and hex screw 1/4-20 UNC x 22.2 [.88] LG.
Figure 16
Bracket Configuration Strokes .5 - 2.50” and 3-6”