Table 10: Input Signal, Power, and Display Specifications
Power Supply
Loop powered from 4-20 mA control signal
Compliance Voltage Rating
9.0 V at 20 mA, 11.0 V at 4.0 mA
Minimum Current Signal to Start Up
3.2 mA
Minimum Input Span for Split Range Operation
5 mA
Upper Range Value for Split Range Operation
8 mA to 20 mA
Lower Range Value for Split Range Operation
4 mA to 14 mA
Wire Size
14/28 AWG
Strip Length
0.22 in / 6 mm
Digital Communication
HART
®
Communication protocol revision 5 or 6
Local Display
LCD, Explosion proof with two lines of nine alpha numeric
characters
Push Buttons
External, Three Explosion Proof / Flameproof push buttons
Table 11: Construction Material Specifications
Housing and Cover
Aluminum ASTM B85 SG100A standard
Stainless Steel optional
Weight
Standard Flow Model:
- Aluminum - 7.4 lbs./ 3.3 kg
- Stainless Steel - 16 lbs/ 7.3 kg
High Flow Model:
- With Display: 9.4 lbs./ 4.2 kg
- Without Display: 8.9 lbs./ 4.0 kg
Relay and Manifold
Standard Flow Model:
Single Acting - PPS, 300 Series Stainless Steel, nitrile diaphragms
Double Acting - 300 Series Stainless Steel, Ryton
Aluminum 6061 T6, Ryton
High Flow Model:
300 Series Stainless Steel, Ryton
Aluminum 6061 T6, Ryton
I/P Motor
430 stainless steel, PPS, 300 series stainless steel
Mounting Bracket
300 series stainless steel
Magnet Holder
Corrosion Protected Anodized Aluminum 6061 T6
Pole Ring
416 stainless steel
Levers
300 Series stainless steel
Masoneilan SVI II AP Digital Positioner Quick Start Guide
=
|
61
© 2015 General Electric Company. All rights reserved
.