Masoneilan SVI II AP Digital Positioner Quick Start Guide
=
|
47
© 2015 General Electric Company. All rights reserved
.
Configuration Menu
Because calibration depends on certain configuration options you must perform Configuration
before you perform Calibration when installing the SVI II AP for the first time.
If a change is made in the Air-to-Open / Air-to-Close configuration option or if you move the SVI
II AP to a different valve or make any change to the valve position linkage, you must run the find
STOPS calibration again.
Figure 24
CONFIGure Menu