Masoneilan SVI II AP Digital Positioner Quick Start Guide
=
|
69
© 2015 General Electric Company. All rights reserved
.
ES-699 Rev AA
Page 3 of 16
3
MODEL NUMBER DESCRIPTION OF SVI-II AP
“SVI2-abcdefgh” Not all combinations are available.
SVI2-
a
b
c
d
e
f
g
h
0
Generic ( National
Labeling as Required)
1
ES -Easy
Smart (1)
Single Acting
Standard Flow
No Display
No Buttons
Industrial
Hart
4 to 20 MADC
None
FM, CSA,ATEX, IEC
(XP, DIP, IS, NI)
2
SD - Standard
Diagnostics
Remote Sensing
Double Acting
High Capacity
Display
Buttons
Industrial (2)
Retransmit
and Digital
Out (Note
3)
3
AD - Advanced
Diagnostics
Remote Sensing
No Display
No Buttons
Offshore
Plug-in
Electronics
Module
(MNCB)
Retransmit
(Note 4)
FM, CSA ATEX (IS,
NI)
4
OD - On-Line
Diagnostics
Remote Sensing
Display
Buttons
Offshore (2)
ATEX (IS, NI)
5
PC - Process
Controller
Remote Sensing
6
FM, CSA,ATEX,IEC
(XP, DIP, IS, NI)
Nuclear
Style
Pneumatics
Capacity
Display
Electronics
Communication
Option
Hazardous
Certification
(1) Not available in a flameproof housing.
(2) The SVI-II AP may be up-graded in the field by the addition of a display and buttons.
(3) Not available on SVI2-abcdefg0
(4) Retransmit without digital output is available only on SVI2-abcdefg0
4
FLAMEPROOF and DUST IGNITION PROOF REQUIREMENTS
4.1
General
The 1/2 inch NPT fittings must enter the housing at least five full turns. The cover
flange must be clean and free of corrosion products.
4.2
Cable Glands
Certified cable glands are required based on the hazardous area the device is
installed in. That is, the particular cable gland used must have the same certification
as the tick-box checked off on the label (see Section 6).
4.3
Natural gas
Use of a pressurized gas which is ignitable in the presence of air (for example
natural gas) is not allowed as the SVI II AP supply pressure in a flameproof
(protection type “d”) installation.
4.4
Bolting