Masoneilan SVI II AP Digital Positioner Quick Start Guide
=
|
87
© 2015 General Electric Company. All rights reserved
.
General Configuration Notes
The SVI II AP supports two identical contact outputs, SW #1 and SW #2 (Digital Output switches),
that can be logically linked to status bits. The Digital Output switch terminals are solid state con-
tacts. Each switch requires its own power source and must be connected to the appropriate con-
nector on the Electronics Module Terminal Board.
The switches are polarity sensitive and must be connected only to a DC circuit. The switch (+) ter-
minal must be electrically positive with respect to the ( –) terminal. If the (+) terminal is electrically
negative with respect to the (–) terminal, then the switch will conduct.
There must be a series load in the circuit to prevent damage to the switch.
If the switch is con-
nected directly across the power source the current will be limited only by the capacity of the
power source and the switch can be damaged.
This section discusses the necessary precautions when configuring a system.
Switch OFF
Switch ON
V
SWITCH
30 VDC max.
1 V (Switch saturation voltage)
I
SWITCH
0.200 mA (Switch leakage current ) 1 A max.
Incorrect polarity connection results in an
effectively closed connection.
CAUTION
Appendix B.
Optional Switch Load Limits