Masoneilan SVI II AP Digital Positioner Quick Start Guide
=
|
51
© 2015 General Electric Company. All rights reserved
.
Auto Tune
This process takes 3 to 10 minutes and strokes the valve in large and small steps to set the PID
parameters for best positioning response.
WARNING
DO NOT perform STOPS while the valve is controlling the process.
DO NOT perform Auto Tune while the valve is controlling the
process.
To auto tune the SVI II AP:
1. Press
*
to begin the autoTUNE procedure.
As autoTUNE proceeds, numerical messages display, indicating the procedure is
working.
2. When autoTUNE is complete,
TUNE
appears.
3. Press
+
repeatedly until
SETUP
appears.
4. Press
* t
o return to SETUP menu;
CALIB
appears.