4.2.10 TRACE MEMORY
Figure 4–10: SETPOINTS PAGE 1 – PQM SETUP / TRACE MEMORY
]] SETPOINTS
]] S1 PQM SETUP
TRACE MEMORY USAGE:
1 x 36 cycles
]] SETPOINTS
]] S2 SYSTEM SETUP
SETPOINT
Range: 1 x 36, 2 x 18, 3 x 12 cycles
] EVENT RECORDER
]
] TRACE MEMORY
]
TRACE MEMORY TRIGGER
MODE: ONE SHOT
Ia OVERCURRENT TRIG
LEVEL: OFF % CT
Ib OVERCURRENT TRIG
LEVEL: OFF % CT
Ic OVERCURRENT TRIG
LEVEL: OFF % CT
In OVERCURRENT TRIG
LEVEL: OFF % CT
Va OVERVOLTAGE TRIG
LEVEL: OFF % NOMINAL
Vb OVERVOLTAGE TRIG
LEVEL: OFF % NOMINAL
Vc OVERVOLTAGE TRIG
LEVEL: OFF % NOMINAL
Va UNDERVOLTAGE TRIG
LEVEL: OFF % NOMINAL
Vb UNDERVOLTAGE TRIG
LEVEL: OFF % NOMINAL
Vc UNDERVOLTAGE TRIG
LEVEL: OFF % NOMINAL
SWITCH INPUT A TRIG:
OFF
SWITCH INPUT B TRIG:
OFF
SWITCH INPUT C TRIG:
OFF
SWITCH INPUT D TRIG:
OFF
Range: ONE SHOT, RETRIGGER
Range: 1 to 150; Step 1%
TRACE MEMORY TRIGGER
DELAY: 0 cycles
TRACE MEMORY TRIGGER
RELAY: OFF
Range: OFF, OPEN-TO-CLOSED,
CLOSED-TO-OPEN
Range: 0 to 30;
Step: 2 cycles
Range: OFF, AUX1,
AUX2, AUX3, ALARM
Range: 1 to 150; Step 1%
Range: 1 to 150; Step 1%
Range: 1 to 150; Step 1%
Range: 1 to 150; Step 1%
Range: 20 to 150; Step 1%
Range: 20 to 150; Step 1%
Range: 20 to 150; Step 1%
Range: 20 to 150; Step 1%
Range: 20 to 150; Step 1%
Range: OFF, OPEN-TO-CLOSED,
CLOSED-TO-OPEN
Range: OFF, OPEN-TO-CLOSED,
CLOSED-TO-OPEN
Range: OFF, OPEN-TO-CLOSED,
CLOSED-TO-OPEN
M E S S A G E
M E S S A G E
M E S S A G E
Summary of Contents for Power Quality Meter Series
Page 2: ......
Page 4: ......
Page 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Page 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Page 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Page 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Page 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Page 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Page 281: ...GE Power Management PQM Power Quality Meter NOTES ...