GE Power Management
PQM Power Quality Meter
8-5
8 DNP COMMUNICATIONS
8.1 DNP 3.0 PROTOCOL
8
8.1.5 BINARY INPUT / BINARY INPUT CHANGE POINT LIST
POINT LIST FOR:
BINARY INPUT (OBJECT 01) / BINARY INPUT CHANGE (OBJECT 02)
INDEX
DESCRIPTION
EVENT CLASS
ASSIGNED TO
NOTES
0
Alarm condition(s) active
Class 1
1
Clock not set
Class 1
Note 1
2
Clock drifting
Class 1
3
Internal error: ADC reference out of range
Class 1
4
Internal error: HC705 processor not responding
Class 1
5
Internal error: switch input circuit fault
Class 1
6
PQM (display) option installed
Class 1
7
T20 (4-20 mA transducer) option installed
Class 1
8
T1 (0-1 mA transducer) option installed
Class 1
9
C (control) option installed
Class 1
10
A (power analysis) option installed
Class 1
11
Switch A closed
Class 1
12
Switch B closed
Class 1
13
Switch C closed
Class 1
14
Switch D closed
Class 1
15
Alarm relay energized
Class 1
16
Auxiliary relay 1 energized
Class 1
17
Auxiliary relay 2 energized
Class 1
18
Auxiliary relay 3 energized
Class 1
19
Aux 1 relay LED active
Class 1
20
Aux 2 relay LED active
Class 1
21
Aux 3 relay LED active
Class 1
22
Alarm LED active
Class 1
23
Program LED active
Class 1
24
Simulation LED active
Class 1
25
Alarm relay LED active
Class 1
26
Self test LED active
Class 1
27
Aux 1 relay LED solid (not flashing)
Class 1
28
Aux 2 relay LED solid (not flashing)
Class 1
29
Aux 3 relay LED solid (not flashing)
Class 1
30
Alarm LED solid (not flashing)
Class 1
31
Program LED solid (not flashing)
Class 1
32
Simulation LED solid (not flashing)
Class 1
33
Alarm relay LED solid (not flashing)
Class 1
34
Self test LED solid (not flashing)
Class 1
35
Alarm active: phase undercurrent
Class 1
36
Alarm active: phase overcurrent
Class 1
37
Alarm active: neutral overcurrent
Class 1
38
Alarm active: undervoltage
Class 1
39
Alarm active: overvoltage
Class 1
40
Alarm active: current unbalance
Class 1
Note 1: This point is also reflected in the corresponding internal indication (IIN) bit in each response header.
Summary of Contents for Power Quality Meter Series
Page 2: ......
Page 4: ......
Page 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Page 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Page 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Page 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Page 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Page 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Page 281: ...GE Power Management PQM Power Quality Meter NOTES ...