GE Power Management
PQM Power Quality Meter
7-29
7 MODBUS COMMUNICATIONS
7.3 MODBUS MEMORY MAP
7
DEMAND
continued
0429
Time - Seconds of React Pwr Dmd Max
---
---
---
F23
N/A
042A
Date - Month/Day of React Pwr Dmd Max
---
---
---
F24
N/A
042B
Date - Year of React Pwr Dmd Max
---
---
---
F25
N/A
042C
Time - Hour/Min of App. Pwr Dmd Max
---
---
---
F22
N/A
042D
Time - Seconds of Apparent Pwr Dmd Max
---
---
---
F23
N/A
042E
Date - Month/Day of App. Pwr Dmd Max
---
---
---
F24
N/A
042F
Date - Year of Apparent Pwr Dmd Max
---
---
---
F25
N/A
0430
Reserved
to
↓
↓
↓
↓
↓
↓
043F
Reserved
FREQUENCY
0440
Frequency
---
---
0.01 x Hz
F1
N/A
0441
Frequency Minimum
---
---
0.01 x Hz
F1
N/A
0442
Frequency Maximum
---
---
0.01 x Hz
F1
N/A
0443
Time - Hours/Min of Frequency Max
---
---
---
F22
N/A
0444
Time - Seconds of Frequency Max
---
---
---
F23
N/A
0445
Date - Month/Day of Frequency Max
---
---
---
F24
N/A
0446
Date - Year of Frequency Max
---
---
---
F25
N/A
0447
Time - Hours/Min of Frequency Min
---
---
---
F22
N/A
0448
Time - Seconds of Frequency Min
---
---
---
F23
N/A
0449
Date - Month/Day of Frequency Min
---
---
---
F24
N/A
044A
Date - Year of Frequency Min
---
---
---
F25
N/A
044B
Reserved
to
↓
↓
↓
↓
↓
↓
044F
Reserved
PULSE INPUT
COUNTERS
0450
Pulse Input 1 (high)
---
---
---
F3
N/A
0451
Pulse Input 1 (low)
---
---
---
F3
N/A
0452
Pulse Input 2 (high)
---
---
---
F3
N/A
0453
Pulse Input 2 (low)
---
---
---
F3
N/A
0454
Pulse Input 3 (high)
---
---
---
F3
N/A
0455
Pulse Input 3 (low)
---
---
---
F3
N/A
0456
Pulse Input 4 (high)
---
---
---
F3
N/A
0457
Pulse Input 4 (low)
---
---
---
F3
N/A
ANALOG
INPUT
0458
Main/Alternate Analog Input (High)
---
---
---
F3
N/A
0459
Main/Alternate Analog Input (low)
---
---
---
F3
N/A
045A
Reserved
to
↓
↓
↓
↓
↓
↓
045F
Reserved
PULSE INPUT
COUNTERS
0460
Totalized Pulse Input (high)
---
---
---
F3
N/A
0461
Totalized Pulse Input (low)
---
---
---
F3
N/A
0462
Pulse Count Cleared Time – Hours/Min
---
---
---
F22
N/A
0463
Pulse Count Cleared Time – Seconds
---
---
---
F23
N/A
0464
Pulse Count Cleared Date – Month/Day
---
---
---
F24
N/A
0465
Pulse Count Cleared Date – Year
---
---
---
F25
N/A
Table 7–10: PQM MEMORY MAP (Sheet 15 of 40)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY DEFAULT
Notes:
* Data type depends on the Command Operation Code.
** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.
**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.
Summary of Contents for Power Quality Meter Series
Page 2: ......
Page 4: ......
Page 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Page 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Page 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Page 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Page 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Page 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Page 281: ...GE Power Management PQM Power Quality Meter NOTES ...