GE Power Management
PQM Power Quality Meter
7-49
7 MODBUS COMMUNICATIONS
7.3 MODBUS MEMORY MAP
7
POWER
FACTOR
ALARMS
continued
1184
Power Factor Lag 2 Relay
0 to 4
1
---
F29
0=OFF
1185
Power Factor Lag 2 Pickup Level
0 to 100
1
0.01 x PF
F1
1.00
1186
Power Factor Lag 2 Dropout Level
0 to 100
1
0.01 x PF
F1
1.00
1187
Power Factor Lag 2 Delay
5 to 6000
5
0.1 x s
F1
100=10.0 s
1188
Reserved
to
↓
↓
↓
↓
↓
↓
118F
Reserved
DEMAND
ALARMS
1190
Phase A Current Demand Relay
0 to 4
1
---
F29
0=OFF
1191
Phase A Current Demand Level
10 to 7500
1
A
F1
100 A
1192
Phase B Current Demand Relay
0 to 4
1
---
F29
0=OFF
1193
Phase B Current Demand Level
10 to 7500
1
A
F1
100 A
1194
Phase C Current Demand Relay
0 to 4
1
---
F29
0=OFF
1195
Phase C Current Demand Level
10 to 7500
1
A
F1
100 A
1196
Neutral Current Demand Relay
0 to 4
1
---
F29
0=OFF
1197
Neutral Current Demand Level
10 to 7500
1
A
F1
100 A
1198
Positive Real Power Demand Relay
0 to 4
1
---
F29
0=OFF
1199
Positive Real Power Demand Level
1 to 65000
1
kW
F1
1000 kW
119A
Positive Reactive Power Demand Relay
0 to 4
1
---
F29
0=OFF
119B
Positive Reactive Power Demand Level
1 to 65000
1
kvar
F1
1000 kvar
119C
Apparent Power Demand Relay
0 to 4
1
---
F29
0=OFF
119D
Apparent Power Demand Level
1 to 65000
1
kVA
F1
1000 kVA
119E
Negative Real Power Demand Relay
0 to 4
1
---
F29
0=OFF
119F
Negative Real Power Demand Level
1 to 65000
1
kW
F1
1000 kW
11A0
Negative Reactive Power Demand Relay
0 to 4
1
---
F29
0=OFF
11A1
Negative Reactive Power Demand Level
1 to 65000
1
kvar
F1
1000 kvar
11A2
Reserved
to
↓
↓
↓
↓
↓
↓
11A7
Reserved
PULSE
INPUT
ALARMS
11A8
Pulse Input 1 Relay
0 to 4
1
---
F29
0=OFF
11A9
Pulse Input 1 Level
1 to 65000
1
---
F1
100
11AA
Pulse Input 1 Delay
5 to 6000
5
0.1 x s
F1
100=10.0 s
11AB
Reserved
to
↓
↓
↓
↓
↓
↓
11AF
Reserved
MISC.
ALARMS
11B0
Serial COM1 Failure Alarm Delay
5 to 61***
1
s
F1
61=OFF
11B1
Serial COM2 Failure Alarm Delay
5 to 61***
1
s
F1
61=OFF
11B2
Clock Not Set Alarm
0 to 1
1
---
F11
1 = ENABLE
11B3
Data Log 1 Percentage Full Alarm Level
50 to 101***
1
s
F1
101=OFF
11B4
Data Log 2 Percentage Full Alarm Level
50 to 101***
1
s
F1
101=OFF
11B5
Reserved
11B6
Reserved
11B7
Reserved
Table 7–10: PQM MEMORY MAP (Sheet 35 of 40)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS and
SCALE
FORMAT
FACTORY DEFAULT
Notes:
* Data type depends on the Command Operation Code.
** Any valid Actual Values or Setpoints address.
*** Maximum Setpoint value represents “OFF”.
**** Minimum Setpoint value represents “OFF”.
***** Maximum Setpoint value represents “UNLIMITED”.
Summary of Contents for Power Quality Meter Series
Page 2: ......
Page 4: ......
Page 10: ...vi PQM Power Quality Meter GE Power Management TABLE OF CONTENTS ...
Page 46: ...2 22 PQM Power Quality Meter GE Power Management 2 2 ELECTRICAL 2 INSTALLATION 2 ...
Page 56: ...3 10 PQM Power Quality Meter GE Power Management 3 4 DEFAULT MESSAGES 3 OPERATION 3 ...
Page 166: ...6 20 PQM Power Quality Meter GE Power Management 6 6 POWER ANALYSIS 6 SOFTWARE 6 ...
Page 274: ...B 4 PQM Power Quality Meter GE Power Management B 1 TABLES AND FIGURES APPENDIXB B ...
Page 276: ...C 2 PQM Power Quality Meter GE Power Management C 1 PQM WARRANTY APPENDIXC C ...
Page 281: ...GE Power Management PQM Power Quality Meter NOTES ...